ACWU90 (–40°C) XLPE 600 Volts 90°C

Send link to this page print Your Nexans contact on this page
ACWU90 (–40°C) XLPE 600 Volts 90°C ARMOURED DIRECT BURIAL CABLE FOR MULTI-UNIT RESIDENTIAL, COMMERCIAL AND SOME INDUSTRIAL FEEDERS
Standards
National  CSA C22.2 N° 51-95
Description

CSA File #LL23462 Class 5811 01 - Cable
CSA File #LL19376 Class 5818 01 - Hazardous Location Cable

 

One to four compact ACM aluminum conductors with low temperature EXELENE* cross-linked polyethylene insulation (RW90 XLPE) and bare aluminum bonding wire in multi-conductor cables. Single conductor cables have aluminum concentric bonding wire. Conductor assembly is wrapped and enclosed in an interlocked aluminum armour with an overall low acid gas and low flame spread, sunlight resistant PVC jacket (LAG/LFS) with FT4 and AG14 rating.  LEAD FREE and RoHS compliant.
#8 and larger are HL rated for Class I Div 1 & 2 Groups A, B, C & D, Class II Div 1 & 2 Groups E, F & G and Class III Hazardous Locations.

 

Application

For exposed and concealed wiring in dry or wet locations and where exposed to the weather.  Nexans cables are marked "SUN RES" for sunlight resistant.
For use in ventilated, non-ventilated and ladder type cable trays in wet and dry locations.
For direct earth burial (with protection as required by Inspection Authority).
For service entrance above or below ground.
For use in hazardous locations with approved connectors.
Minimum recommended installation temperature minus 40°C (with suitable handling procedures).
Maximum conductor temperature 90°C.

Rated 600 volts. 


 TOP
ACWU Single Stranded Conductor (plus bonding wire)

Size **
AWG or
kcmil

Insulation 
Thickness

Bonding 
Wire 
Size 
AWG

Approximate 
Diameter

Approximate 
Net Cable
Weight 

Ampacity*** 
(amps) 
30°C 
Ambient 

mm

in

Armour

PVC Jacket

mm

in

mm

in

kg/km

lbs/kft

1/0

1.40

0.055

18.9

0.74

21.7

0.85

563

378

190

2/0

1.40

0.055

20.7

0.81

23.1

0.91

690

464

220

3/0

1.40

0.055

21.6

0.85

24.3

0.96

761

511

255

4/0

1.40

0.055

23.1

0.91

25.6

1.01

848

570

300

250

1.65

0.065

24.9

0.98

27.3

1.08

1007

677

330

300

1.65

0.065

26.1

1.03

28.6

1.13

1098

738

375

350

1.65

0.065

27.8

1.10

30.6

1.20

1265

850

415

400

1.65

0.065

28.8

1.14

31.4

1.23

1338

900

450

500

1.65

0.065

31.3

1.23

34.0

1.34

1619

1088

515

600

2.03

0.080

34.0

1.34

36.7

1.45

1843

1239

585

750

2.03

0.080

1/0 

36.8

1.45

39.5

1.56

2210

1485

670

1000

2.03

0.080

1/0 

40.7

1.60

43.4

1.71

2660

1787

800

#1250 

2.41

0.095

2/0 

47.3

1.87

50.6

1.99

3735

2507

905

#1500

2.41

0.095

3/0 

51.4

2.02

54.7

2.16

4355

2925

1020

Insulation Colour Code:  Black
** Compact aluminum conductors are AA-8000 series aluminum alloy (ACM)
***Ampacity in accordance with Table #3 of the Canadian Electrical Code Part #1.
#Conductors are compressed stranding not compact.


ACWU Three Stranded Conductor (plus bonding wire)

Size**
 AWG
or
kcmil

Insulation 
Thickness

Bonding 
Wire 
Size 
AWG

Approximate 
Diameter

Approximate 
Net Cable
Weight 

Ampacity*** 
(amps) 
30°C 
Ambient

Armour

PVC Jacket

mm

in

mm

in

mm

in

kg/km

lbs/kft

6

1.14

0.045

8

20.6

0.81

23.6

0.93

500

335

55#

4

1.14

0.045

6

23.1

0.91

25.9

1.02

618

415

65

3

1.14

0.045

6

24.4

0.96

27.2

1.07

673

452

75

2

1.14

0.045

6

25.9

1.02

28.7

1.13

771

518

95#

1

1.40

0.055

4

28.9

1.14

31.7

1.25

941

632

105

1/0

1.40

0.055

4

31.0

1.22

33.5

1.32

1074

722

120

2/0

1.40

0.055

4

33.0

1.30

35.8

1.41

1235

830

145

3/0

1.40

0.055

4

35.8

1.41

38.3

1.51

1444

970

165

4/0

1.40

0.055

4

38.6

1.52

41.9

1.65

1746

1173

185#

250

1.65

0.065

2

42.2

1.66

45.5

1.79

2165

1455

215

300

1.65

0.065

2

45.7

1.80

48.8

1.92

2661

1788

240

350

1.65

0.065

2

48.3

1.90

51.6

2.03

2958

1989

260

400

1.65

0.065

2

50.3

1.98

53.6

2.11

3234

2173

290

500

1.65

0.065

1

54.9

2.16

58.2

2.29

3767

2531

330

600

2.03

0.080

1

60.4

2.38

64.5

2.54

4561

3065

370

750

2.03

0.080

1/0

65.7

2.59

70.0

2.74

5423

3644

405

Insulation Colour Code:  Black, Red, White
**Compact aluminum ACM conductors are aluminum alloy #8030
***Ampacity in accordance with Table #4 of the Canadian Electrical Code Part #1.
# For 3-wire 120/240 V and 120/208 V service conductors for single dwellings, or for feeder 
conductors supplying single dwelling units of row housing, of apartments and similar 
buildings, and sized in accordance with Rules 8-200(1), 8-200(2) and 8-202(1), the 
allowable ampacity for sizes No. 6, No. 2 and No. 4/0 AWG shall be 60 A, 100 A 
and 200 A respectively.  In this case the 5% adjustment Rule 8-106(1) cannot be applied.


ACWU Four Stranded Conductor (plus bonding wire)

Size**
 AWG
or
kcmil

Insulation 
Thickness

Bonding 
Wire
Size 
AWG

Approximate 
Diameter

Approximate 
Net Cable
Weight 

Ampacity*** 
(amps) 
30°C 
Ambient

Armour

PVC Jacket

mm

in

mm

in

mm

in

kg/km

lbs/kft

6

1.14

0.045

8

22.6

0.89

25.6

1.01

583

392

55#

4

1.14

0.045

6

25.4

1.00

28.7

1.13

774

520

65

3

1.14

0.045

6

26.9

1.06

29.4

1.16

818

550

75

2

1.14

0.045

6

28.7

1.13

31.2

1.23

932

626

95#

1

1.40

0.055

4

32.0

1.26

34.8

1.37

1143

768

105

1/0 

1.40

0.055

4

34.3

1.35

36.8

1.45

1323

889

120

2/0 

1.40

0.055

4

36.6

1.44

39.1

1.54

1533

1030

145

3/0 

1.40

0.055

4

39.4

1.55

42.4

1.67

1839

1236

165

4/0 

1.40

0.055

4

42.4

1.67

45.7

1.80

2168

1457

185#

250 

1.65

0.065

2

47.2

1.86

50.5

1.99

2897

1947

215

300 

1.65

0.065

2

50.2

1.98

53.5

2.11

3289

2210

240

350 

1.65

0.065

2

53.0

2.09

56.3

2.22

3612

2427

260

400 

1.65

0.065

2

55.6

2.19

58.9

2.32

3966

2665

290

500 

1.65

0.065

1

60.4

2.38

64.5

2.54

4834

3248

330

600 

2.03

0.080

1

67.0

2.64

70.9

2.79

5725

3847

370

750 

2.03

0.080

1/0 

72.9

2.87

76.7

3.02

6860

4610

405

Insulation Colour Code:  Black, Red, Blue, White
**Compact aluminum ACM conductors are aluminum alloy #8030
***Ampacity in accordance with Table #4 of the Canadian Electrical Code Part #1 and 
assuming the fourth conductor is the neutral of a balanced 3 phase, 4 wire system.
# For 3-wire 120/240 V and 120/208 V service conductors for single dwellings, or for feeder 
conductors supplying single dwelling units of row housing, of apartments and similar 
buildings, and sized in accordance with Rules 8-200(1), 8-200(2) and 8-202(1), the 
allowable ampacity for sizes No. 6, No. 2 and No. 4/0 AWG shall be 60 A, 100 A 
and 200 A respectively.  In this case the 5% adjustment Rule 8-106(1) cannot be applied.