ACWU90 (–40°C) XLPE 600 Volts 90°C

Send link to this page print Your Nexans contact on this page
ACWU90 (–40°C) XLPE 600 Volts 90°C ARMOURED DIRECT BURIAL CABLE FOR MULTI-UNIT RESIDENTIAL, COMMERCIAL AND INDUSTRIAL FEEDERS
Standards
National  CSA C22.2 N° 51-95
Description

CSA File #LL23462 Class 5811 01 - Cable
CSA File #LL19376 Class 5818 01 - Hazardous Location Cable

 

One to four compact ACM aluminum conductors with low temperature, sunlight resistant (black and colours) EXELENE* cross-linked polyethylene insulation (RW90 XLPE) and bare aluminum bonding wire in multi-conductor cables. Single conductor cables have aluminum concentric bonding wire. Conductor assembly is wrapped and enclosed in an interlocked aluminum armour with an overall low acid gas and low flame spread, sunlight resistant PVC jacket (LAG/LFS) with FT4 and AG14 rating.  LEAD FREE and RoHS compliant.
#8 and larger are HL rated for Class I Div 1 & 2 Groups A, B, C & D, Class II Div 1 & 2 Groups E, F & G and Class III Hazardous Locations.

 

Application

For exposed and concealed wiring in dry or wet locations and where exposed to the weather.  Nexans cables are marked "SUN RES" for sunlight resistant.
For use in ventilated, non-ventilated and ladder type cable trays in wet and dry locations.
For direct earth burial (with protection as required by Inspection Authority).
For service entrance above or below ground.
For use in hazardous locations with approved connectors.
Minimum recommended installation temperature minus 40°C (with suitable handling procedures).
Maximum conductor temperature 90°C.

Rated 600 volts. 


 TOP
Characteristics
Construction characteristics
Conductor material Aluminium  
Electrical characteristics
Maximum operating voltage 600V  
Usage characteristics
Maximum operating temperature 90°C  

 TOP
ACWU Single Stranded Conductor (plus bonding wire)

Size **
AWG or
kcmil

Insulation 
Thickness

Bonding 
Wire 
Size 
AWG or
kcmil

Approximate 
Diameter

Approximate 
Net Cable
Weight 

Ampacity*** 
(amps) 
30°C 
Ambient 

mm

in

Armour

PVC Jacket

mm

in

mm

in

kg/km

lbs/kft

1/0

1.40

0.055

4

20.10

0.791

22.79

0.897

521

360

190

2/0

1.40

0.055

2

22.71

0.894

25.38

0.999

636

439

220

3/0

1.40

0.055

2

23.90

0.941

26.59

1.047

707

488

255

4/0

1.40

0.055

2

24.99

0.984

27.59

1.086

779

538

300

250

1.65

0.065

1

26.82

1.056

29.57

1.164

941

650

330

300

1.65

0.065

1

28.14

1.108

28.60

1.216

1043

720

375

350

1.65

0.065

1/0

29.21

1.150

31.45

1.238

1115

770

415

400

1.65

0.065

1/0

30.42

1.198

31.40

1.306

1227

847

450

500

1.65

0.065

2/0

31.30

1.263

34.80

1.370

1422

982

515

600

2.03

0.080

2/0

35.05

1.380

36.70

1.488

1645

1136

585

750

2.03

0.080

3/0

36.80

1.490

40.59

1.598

1961

1354

670

1000

2.03

0.080

3/0

40.70

1.638

44.32

1.745

2392

1652

800

#1250 

2.41

0.095

4/0

47.50

1.870

50.60

1.990

3735

2507

905

#1500

2.41

0.095

250

51.31

2.020

54.70

2.160

4355

2925

1020

Insulation Colour Code:  Black (sunlight resistant)
** Compact aluminum conductors are AA-8000 series aluminum alloy (ACM)
***Ampacity in accordance with Table #3 of the Canadian Electrical Code Part #1.
#Conductors are compressed stranding not compact.


ACWU Three Stranded Conductor (plus bonding wire)

Size**
 AWG
or
kcmil

Insulation 
Thickness

Bonding 
Wire 
Size 
AWG

Approximate 
Diameter

Approximate 
Net Cable
Weight 

Ampacity*** 
(amps) 
30°C 
Ambient

Armour

PVC Jacket

mm

in

mm

in

mm

in

kg/km

lbs/kft

6

1.14

0.045

8

20.6

0.81

23.6

0.93

500

335

55#

4

1.14

0.045

6

23.1

0.91

25.9

1.02

618

415

65

3

1.14

0.045

6

24.4

0.96

27.2

1.07

673

452

75

2

1.14

0.045

6

25.9

1.02

28.7

1.13

771

518

95#

1

1.40

0.055

4

28.9

1.14

31.7

1.25

941

632

105

1/0

1.40

0.055

4

31.0

1.22

33.5

1.32

1074

722

120

2/0

1.40

0.055

4

33.0

1.30

35.8

1.41

1235

830

145

3/0

1.40

0.055

4

35.8

1.41

38.3

1.51

1444

970

165

4/0

1.40

0.055

4

38.6

1.52

41.9

1.65

1746

1173

185#

250

1.65

0.065

2

42.2

1.66

45.5

1.79

2165

1455

215

300

1.65

0.065

2

45.7

1.80

48.8

1.92

2661

1788

240

350

1.65

0.065

2

48.3

1.90

51.6

2.03

2958

1989

260

400

1.65

0.065

2

50.3

1.98

53.6

2.11

3234

2173

290

500

1.65

0.065

1

54.9

2.16

58.2

2.29

3767

2531

330

600

2.03

0.080

1

60.4

2.38

64.5

2.54

4561

3065

370

750

2.03

0.080

1/0

65.7

2.59

70.0

2.74

5423

3644

405

Insulation Colour Code:  Black, Red, White (all sunlight resistant)
**Compact aluminum ACM conductors are aluminum alloy #8030
***Ampacity in accordance with Table #4 of the Canadian Electrical Code Part #1.
# For 3-wire 120/240 V and 120/208 V service conductors for single dwellings, or for feeder 
conductors supplying single dwelling units of row housing, of apartments and similar 
buildings, and sized in accordance with Rules 8-200(1), 8-200(2) and 8-202(1), the 
allowable ampacity for sizes No. 6, No. 2 and No. 4/0 AWG shall be 60 A, 100 A 
and 200 A respectively.  In this case the 5% adjustment Rule 8-106(1) cannot be applied.


ACWU Four Stranded Conductor (plus bonding wire)

Size**
 AWG
or
kcmil

Insulation 
Thickness

Bonding 
Wire
Size 
AWG

Approximate 
Diameter

Approximate 
Net Cable
Weight 

Ampacity*** 
(amps) 
30°C 
Ambient

Armour

PVC Jacket

mm

in

mm

in

mm

in

kg/km

lbs/kft

6

1.14

0.045

8

22.6

0.89

25.6

1.01

583

392

55#

4

1.14

0.045

6

25.4

1.00

28.7

1.13

774

520

65

3

1.14

0.045

6

26.9

1.06

29.4

1.16

818

550

75

2

1.14

0.045

6

28.7

1.13

31.2

1.23

932

626

95#

1

1.40

0.055

4

32.0

1.26

34.8

1.37

1143

768

105

1/0 

1.40

0.055

4

34.3

1.35

36.8

1.45

1323

889

120

2/0 

1.40

0.055

4

36.6

1.44

39.1

1.54

1533

1030

145

3/0 

1.40

0.055

4

39.4

1.55

42.4

1.67

1839

1236

165

4/0 

1.40

0.055

4

42.4

1.67

45.7

1.80

2168

1457

185#

250 

1.65

0.065

2

47.2

1.86

50.5

1.99

2897

1947

215

300 

1.65

0.065

2

50.2

1.98

53.5

2.11

3289

2210

240

350 

1.65

0.065

2

53.0

2.09

56.3

2.22

3612

2427

260

400 

1.65

0.065

2

55.6

2.19

58.9

2.32

3966

2665

290

500 

1.65

0.065

1

60.4

2.38

64.5

2.54

4834

3248

330

600 

2.03

0.080

1

67.0

2.64

70.9

2.79

5725

3847

370

750 

2.03

0.080

1/0 

72.9

2.87

76.7

3.02

6860

4610

405

Insulation Colour Code:  Black, Red, Blue, White (all sunlight resistant)
**Compact aluminum ACM conductors are aluminum alloy #8030
***Ampacity in accordance with Table #4 of the Canadian Electrical Code Part #1 and 
assuming the fourth conductor is the neutral of a balanced 3 phase, 4 wire system.
# For 3-wire 120/240 V and 120/208 V service conductors for single dwellings, or for feeder 
conductors supplying single dwelling units of row housing, of apartments and similar 
buildings, and sized in accordance with Rules 8-200(1), 8-200(2) and 8-202(1), the 
allowable ampacity for sizes No. 6, No. 2 and No. 4/0 AWG shall be 60 A, 100 A 
and 200 A respectively.  In this case the 5% adjustment Rule 8-106(1) cannot be applied.