RW90 (–40°C) XLPE Insulated Wire 90°C

Send link to this page print Your Nexans contact on this page
RW90 (–40°C) XLPE Insulated Wire 90°C RW90 (–40°C) XLPE Service Entrance or Supply wire
Standards
National  CSA C22.2 N° 38-05 
Description

CSA File #LL23462 Class 5832 03

 

Single copper or compact ACM aluminum conductor with low temperature moisture resisting Exelene* cross-linked polyethylene insulation.  LEAD FREE.

 

Application

For open wiring and raceways (except cabletroughs and ventilated flexible cableway) in dry or wet locations.
For exposed wiring where exposed to weather with sunlight resistant insulation. Standard Black #6 and larger is sunlight resistant and marked "SR"; coloured insulation is NOT.
Minimum recommended installation temperature minus 40°C (with suitable handling procedures).
Maximum conductor temperature 90°C.
Approved for use with ceiling fixtures.


 TOP
Characteristics
Usage characteristics
Maximum operating temperature 90°C  

 TOP
Your selection
Operating voltage  V
Conductor material  
Apply
Reset
Results   4/4
Select all Items Nexans ref. Name Operating voltage (V) Conductor material
RW90 (–40°C) XLPE Insulated Wire 1 kV 90°C Al RW90 (–40°C) XLPE Insulated Wire 1 kV 90°C Al 1000 Aluminium
RW90 (–40°C) XLPE Insulated Wire 1 kV 90°C Cu RW90 (–40°C) XLPE Insulated Wire 1 kV 90°C Cu 1000 Copper
RW90 (–40°C) XLPE Insulated Wire 600 V 90°C AL RW90 (–40°C) XLPE Insulated Wire 600 V 90°C Al 600 Aluminium
RW90 (–40°C) XLPE Insulated Wire 600 V 90°C Cu RW90 (–40°C) XLPE Insulated Wire 600 V 90°C Cu 600 Copper
Add to favorites

 TOP
Selling delivery information

Colours: Standard colours are available.

Non-jacketed RW-90 (XLPE) cables are not suitable for installation in vaults and switchrooms under the conditions of C.E. Code Part 1 Rule 12-2202(3). Suitable flame retardant jacketed cables are available on request.

#For 3-wire 120/240 and 120/208V residential services or sub-services, the allowable ampacity for sizes #6, #2 and #4/0 AWG aluminum shall be 60, 100 and 200 amperes respectively. #2/0 AWG copper shall be 200 amperes. In these cases, the 5% adjustment per C.E. Code Rule 8-106(1) cannot be applied.

## Based on not more than 3 copper or aluminum conductors in raceway or cable.