FIREX®-II 1C TECK 90 (XLPE) -40ºC 5 kV Unshielded

Send link to this page print Your Nexans contact on this page
Nexans FIREX®-II TECK Cables are intended for use in various primary and secondary industries, including chemical processing plants, refineries and general factory environments.
Standards
National  CSA C22.2 N° 131
Description

Even in the most demanding industrial and resource industry applications, Nexans FIREX®-II TECK cables have proven to have a superior service and maintenance record. 

FIREX®-II TECK cables utilize low acid gas, low flame spread PVC jacket compounds to ensure maximum safety to personnel and equipment in the event of fire.

 

Applications

FIREX®-II TECK Cables, originally developed for use in Canadian mines, are flexible, resistant to mechanical abuse, corrosion resistant, compact and reliable. They are suitable for a wide range of applications, including ALL hazardous locations.

Industries such as pulp and paper, chemical, petroleum and other primary and secondary manufacturing industries have used FIREX®-II TECK Cables, particularly in areas where cables are subject to the risk of mechanical damage and chemical attack.

Commercial applications for FIREX®-II TECK Cables include apartment buildings and commercial complexes.

FIREX®-II TECK Cables can be relocated easily because they are rugged and flexible. They can be used in both dry and wet locations in open wiring, in ventilated, nonventilated and ladder-type cable troughs, in ventilated flexible cableways, and for direct burial.

TECK Cables are also suitable for service entrance installations - above and below ground.

Highlights

Nexans FIREX®-II TECK Cables are:

  • Available from stock
  • Versatile
  • Flexible
  • Resistant to Mechanical Abuse and Corrosion
  • Compact and Reliable
  • "HL" and "FT4" Rated per CSA
  • 90°C to -40°C
  • Low Acid Gas (AG14)
  • LEAD FREE
  • RoHS Compliant

For full design features, standard certifications and construction data, check attached full document.

Marking and Identification

The outer jackets of Nexans FIREX®-II 5 kV TECK cables are printed:  NEXANS FIREX®-II TECK90 XLPE (-40°C) CSA LL19376 F 5 KV NON-SHLD HL FT4 AG14 SUN RES, plus size and number of conductors.


 TOP
1C TECK 90 (XLPE) 5 kV Unshielded with Concentric Bonding Conductor

Conductor
Size

Insulation
Thickness

Inner
Jacket
Thickness

Approximate
Diameters

Approx. 
Weight
Aluminum
Armour*

Copper
Content

Power
AWG
or 
kcmil

Bonding
AWG

Inner
Jacket

Armour

Outer
Covering

inches

mm

inches

mm

inches

mm

inches

mm

inches

mm

lb/kft

kg/km

kg/km

8

10

0.090

2.29

0.060

1.52

0.931

23.64

1.206

30.63

1.315

33.40

721

1073

281

6

8

0.090

2.29

0.080

2.03

1.051

26.69

1.326

33.68

1.435

36.45

872

1298

446

4

8

0.090

2.29

0.080

2.03

1.146

29.11

1.421

36.09

1.530

38.86

1155

1720

665

 

3

6

0.090

2.29

0.080

2.03

1.200

30.49

1.475

37.46

1.584

40.23

1322

1968

866

2

6

0.090

2.29

0.080

2.03

1.266

32.15

1.541

39.14

1.670

42.42

1503

2237

1057

1

6

0.090

2.29

0.080

2.03

1.335

33.91

1.610

40.89

1.739

44.17

1732

2578

1304

 

1/0

6

0.090

2.29

0.080

2.03

1.415

35.95

1.690

42.93

1.819

46.20

2013

2997

1609

2/0

6

0.090

2.29

0.080

2.03

1.500

38.10

1.775

45.09

1.904

48.36

2339

3481

1997

3/0

4

0.090

2.29

0.080

2.03

1.606

40.80

.1.956

49.68

2.090

53.09

2929

4359

2558

4/0

4

0.090

2.29

0.080

2.03

1.724

43.79

2.074

52.68

2.208

56.08

3544

5274

3173

 

250

4

0.090

2.29

0.110

2.79

1.882

47.80

2.232

56.69

2.366

60.10

4032

6001

3716

300

4

0.090

2.29

0.110

2.79

1.990

50.55

2.340

59.44

2.474

62.84

4605

6852

4414

350

3

0.090

2.29

0.110

2.79

2.094

53.19

2.444

62.08

2.578

65.48

5242

7800

5171

 

400

3

0.090

2.29

0.110

2.79

2.188

55.56

2.538

64.47

2.672

67.87

5852

8709

5883

500

3

0.090

2.29

0.110

2.79

2.355

59.81

2.705

68.71

2.839

72.11

7053

10495

7278


1C TECK90 (XLPE) 5 kV Fitting Sizes and Ampacity

Conductor Size

Ampacity
30ºC
Ambient A

Fittings††

Power
AWG or kcmil

Bonding
AWG

Appleton

T & B

CMP
Products

Cooper 
Crouse-
Hinds

6

8

100

TMC5099

10466AL/ST050-466

TMC075A

TECK050-3

4

6

135

TMC75121

10467AL/ST075-467

TMC075A

TECK050-4

 

 

 

 

 

 

 

3

6

155

TMC75121

10467AL/ST075-467

TMC075A

TECK050-4

2

6

180

TMC75121

10467AL/ST075-467

TMC100A

TECK075-5

1

4

210

TMC75121

10468AL/ST075-468

TMC100A

TECK075-6

 

 

 

 

 

 

 

1/0

4

245

TMC100138

10468AL/ST075-468

TMC100A

TECK075-6

2/0

4

285

TMC100138

10469AL/ST075-468

TMC100A

TECK075-6

3/0

3

330

TMC100138

10469AL/ST100-469 

TMC125A

TECK100-7

4/0

3

385

TMC100138

10469AL/ST100-469

TMC125A

TECK100-7

 

 

 

 

 

 

 

250

2

425

TMC125163

10470AL/ST125-470 

TMC125A

TECK125-8

300

2

480

TMC125163

10470AL/ST125-470

TMC125A

TECK125-8

350

1

530

TMC125163

10470AL/ST125-470

TMC150A

TECK125-8

 

 

 

 

 

 

 

400

1

575

TMC125163

10550AL/ST125-550

TMC150A

TECK125-8

500

1/0

660

TMC125188

10471AL/ST125-471

TMC150A

TECK125-10

 

 

 

 

 

 

 

600

1/0

740

TMC125188

10471AL/ST125-471

TMC200SA

TECK125-10

750

2/0

845

TMC150200

10472AL/ST150-472

TMC200SA

TECK125-10

1000

2/0

1000

TMC150220

10551AL/ST200-551

TMC200A

TECK150-11

††Ensure that only nonmagnetic connectors, locknuts and ground bushings are used.


 TOP
Selling delivery information

Caution Notice

In case of fire, well maintained early warning smoke detectors will give an alarm long before non-metallic coverings become combustible.

However, in spite of the widespread and long-standing use of PVC in residential and commercial buildings, all purchasers of PVC insulated/ jacketed products should be aware of the following:
  • Non-metallic coverings of electrical cables can burn and may transmit fire when ignited.
  • Burning non-metallic coverings may emit acid gases which are toxic and may generate dense smoke.
  • Emission of acid gases may corrode metal in the vicinity; e.g. sensitive instruments and reinforcing rods in cement.

Nexans © copyright 2001 - 2010   Legal Notice | Contact Us | Site Map