Colours: Standard colours are available.
Non-jacketed RW-90 (XLPE) cables are not suitable for installation in vaults and switchrooms under the conditions of C.E. Code Part 1 Rule 12-2202(3). Suitable flame retardant jacketed cables are available on request.
#For 3-wire 120/240 and 120/208 V residential services or sub-services, the allowable ampacity for sizes #6, #2 and #4/0 AWG aluminum shall be 60, 100 and 200 amperes respectively. In these cases, the 5% adjustment per C.E. Code Rule 8-106(1) cannot be applied.
## Based on not more than 3 current carrying conductors in raceway or cable.
|