ASC Bare Overhead Conductors
REFERENCES
Overhead Aluminum Stranded Conductors
Standards
Description
Characteristics
Standards
National  CAN/CSA-C61089
Description

 

Bare overhead aluminum stranded conductors (ASC) are concentric-lay-stranded consisting of one or more layers of aluminum alloy 1350 wires wrapped helically around a central wire. Each successive layer has six wires more than the underlying one. Increasing the number of wires for any given cross-sectional area provides greater flexibility. The most commonly used strandings consist of 7, 19, 37, 61 and 91 wires.

Class AA strandings are used for bare overhead lines. The direction of lay for the outer layer is right-hand and is usually reversed in successive layers. The temper of the wires is full hard-drawn (H19).

 

Features and Benefits
ASC conductors are the most economical since their lighter weight means lower unit length costs, easier handling during installation and the use of simpler fittings. They are inherently corrosion resistant due to their homogeneous construction

 

 

Applications
Stranded bare ASC conductors may be used in overhead line installations where the design parameters do not require the higher tensile strength or temperature ratings provided by ACSR, ACCR or other types of conductors.

 


 TOP
Characteristics
Construction characteristics
Conductor material Aluminium  

 TOP
Aluminum Stranded Conductor (ASC) Electrical Data

Codeword

Size
(AWG or
kcmil)

Resistance (Ω/km)

Reactance at 60 Hz**

Ampacity*
(A)

DC at
20°C

AC at
25°C

AC at
50°C

AC at
75°C

Capacitive
(MΩ-km)

Inductive
(Ω/km)

Peachbell

6

2.154

2.207

2.426

2.644

0.233

0.392

103

Rose

4

1.354

1.387

1.525

1.662

0.222

0.374

138

Iris

2

0.852

0.871

0.958

1.044

0.210

0.357

185

Pansy

1

0.675

0.692

0.761

0.829

0.205

0.348

214

Poppy

1/0

0.535

0.548

0.603

0.657

0.199

0.339

247

Aster

2/0

0.425

0.435

0.478

0.521

0.194

0.331

286

Phlox

3/0

0.337

0.346

0.380

0.413

0.188

0.322

331

Oxlip

4/0

0.267

0.274

0.301

0.328

0.183

0.313

383

Daisy

266.8

0.212

0.218

0.239

0.260

0.177

0.304

443

Laurel

266.8

0.213

0.218

0.239

0.260

0.177

0.300

444

Peony

300

0.189

0.193

0.213

0.232

0.174

0.296

478

Tulip

336.4

0.169

0.173

0.190

0.206

0.171

0.291

513

Daffodil

350

0.162

0.166

0.182

0.199

0.170

0.290

526

Canna

397.5

0.143

0.146

0.160

0.175

0.167

0.285

570

Cosmos

477

0.119

0.122

0.134

0.146

0.163

0.278

639

Zinnia

500

0.114

0.117

0.128

0.140

0.162

0.277

658

Dahlia

556.5

0.102

0.105

0.116

0.126

0.159

0.272

703

Orchid

636

0.0895

0.0926

0.101

0.110

0.156

0.266

765

Violet

715.5

0.0796

0.0820

0.0901

0.0982

0.153

0.262

823

Petunia

750

0.0759

0.0787

0.0862

0.0937

0.152

0.260

847

Arbutus

795

0.0716

0.0746

0.0814

0.0883

0.150

0.258

878

Magnolia

954

0.0597

0.0628

0.0684

0.0746

0.146

0.250

982

Bluebell

1033.5

0.0551

0.0580

0.0634

0.0690

0.144

0.248

1031

Marigold

1113

0.0512

0.0542

0.0591

0.0640

0.142

0.244

1079

Hawthorn

1192.5

0.0478

0.0509

0.0555

0.0602

0.141

0.242

1124

Narcissus

1272

0.0448

0.0480

0.0523

0.0566

0.139

0.239

1169

Columbine

1351.5

0.0422

0.0454

0.0494

0.0535

0.138

0.237

1212

Carnation

1431

0.0398

0.0432

0.0470

0.0508

0.136

0.235

1253

Gladiolus

1510.5

0.0377

0.0412

0.0447

0.0484

0.135

0.233

1294

Coreopsis

1590

0.0359

0.0394

0.0428

0.0462

0.134

0.231

1333

Cowslip

2000

0.0285

0.0326

0.0352

0.0378

0.128

0.222

1518

Lupine

2500

0.0228

0.0277

0.0297

0.0318

0.123

0.214

1706

*  Ampacity is with sun and wind at 0.6 m/s
** Reactance at 0.3 meter equivalent spacing


Aluminum Stranded Conductor (ASC) Physical Data

Codeword

Size
(AWG or
kcmil)

No. 
of
wires

Total
Area 
(mm2)

Diameter (mm)

Total Weight
(kg/km)

Rated 
Strength
(kN)

Individual
Wire

Complete
Conductor

Peachbell

6

7

13.30

1.56

4.7

36.4

2.61

Rose

4

7

21.15

1.96

5.9

58.0

4.12

Iris

2

7

33.63

2.47

7.4

92.2

6.21

Pansy

1

7

42.41

2.78

8.3

116.2

7.44

Poppy

1/0

7

53.51

3.12

9.4

146.6

9.10

Aster

2/0

7

67.44

3.50

10.5

184.8

11.45

Phlox

3/0

7

85.03

3.93

11.8

233.0

14.01

Oxlip

4/0

7

107.2

4.42

13.2

293.8

17.72

Daisy

266.8

7

135.2

4.96

14.9

370.5

22.32

Laurel

266.8

19

135.2

3.01

15.0

372.3

22.98

Peony

300

19

152.0

3.19

16.0

418.6

25.82

Tulip

336.4

19

170.5

3.38

16.9

469.4

28.98

Daffodil

350

19

177.4

3.45

17.2

488.4

30.19

Canna

397.5

19

201.4

3.67

18.4

554.6

34.17

Cosmos

477

19

241.7

4.02

20.1

665.6

39.79

Zinnia

500

19

253.4

4.12

20.6

697.7

41.79

Dahlia

556.5

19

282.0

4.35

21.7

776.5

46.59

Orchid

636

37

322.3

3.33

23.3

890

54.78

Violet

715.5

37

362.6

3.53

24.7

1001

61.56

Petunia

750

37

380.0

3.62

25.3

1049

64.74

Arbutus

795

37

402.8

3.72

26.1

1112

68.36

Magnolia

954

37

483.4

4.08

28.5

1334

79.82

Bluebell

1033.5

37

523.7

4.25

29.7

1445

86.61

Marigold

1113

61

564.0

3.43

30.9

1559

95.82

Hawthorn

1192.5

61

604.3

3.55

32.0

1670

102.6

Narcissus

1272

61

644.5

3.67

33.0

1782

109.7

Columbine

1351.5

61

684.8

3.78

34.0

1893

113.0

Carnation

1431

61

725.1

3.89

35.0

2004

119.6

Gladiolus

1510.5

61

765.4

4.00

36.0

2116

126.5

Coreopsis

1590

61

805.7

4.10

36.9

2227

132.9

Cowslip

2000

91

1013

3.77

41.4

2804

167.6

Lupine

2500

91

1267

4.21

46.3

3505

209.0