Triplex Unjacketed NS75/NS90 - Reduced Neutral

Send link to this page print Your Nexans contact on this page
Triplex Unjacketed NS75/NS90 - Reduced Neutral Secondary Distribution Cable
REFERENCES
Neutral Supported Cable
Standards
Description
Characteristics
Related Information
Standards
National  CSA C22.2 N° 129
Description

Nexans’ triplex neutral supported cables consist of an assembly of  two insulated phase conductors factory-cabled around a neutral conductor. The neutral conductor is the supporting member. The conductors are insulated with polyethylene (PE) rated 75 °C or crosslinked polyethylene (XLPE) rated 90 °C.

 

Application

Neutral supported cables are intended for use either as a service drop cable between a power pole and the service entrance, or as a secondary distribution cable between poles. Their use is limited to circuits not exceeding 600 volts phase-to-phase.

Triplex service drop cables are intended to deliver single-phase power from the secondary power line or pole-mounted transformer to the service entrance conductors at the user’s building or other structures.

Optional construction includes an insulated control/supply conductor.


 TOP
Characteristics
Construction characteristics
With smaller neutral conductor Yes  
Number of conductors 3  

 TOP
Triplex Unjacketed NS75/NS90 Reduced Neutral Physical Data

Code Word

Phase Conductor

Reduced  Size Neutral Support

Cable Assembly

Size
(Stranding)
AWG/kcmil

Diameter
(mm)

Insulation
Diameter
(mm)

Size
(Stranding)
(AWG)

Area
(mm²)

Rated
Strength
(kN)

Overall
Diameter
(mm)

Total 
Weight
(kg/km)

Caesium

4 (7)

5.41

7.8

6 (6/1)

15.48

5.20

15.5

217

Indium

2 (7)

6.81

9.2

4 (6/1)

24.71

8.14

18.3

328

-

1 (7)

7.59

10.7

2 (6/1)

39.23

8.14

21.4

457

Rubidium

1/0 (7)

8.53

11.7

2 (6/1)

39.23

12.41

23.3

528

Titanium

2/0 (7)

9.55

12.7

1 (6/1)

49.48

15.48

25.3

650

Palladium

3/0 (7)

10.74

13.9

1/0 (6/1)

62.39

19.08

27.7

800

Strontium

4/0 (7)

12.07

15.2

2/0 (6/1)

78.65

23.80

30.4

1000

-

266.8 (18)

13.64

17.8

3/0 (6/1)

99.23

29.67

35.6

1290

-

336.4 (18)

15.32

19.5

4/0 (6/1)

125.1

37.45

39.0

1600

-

397.5 (18)

16.74

20.9

266.8 (26/7)

157.2

50.10

42.3

1900

-

477 (18)

18.34

22.5

336.4 (26/7)

198.2

62.31

45.9

2280

-

500 (18)

18.69

22.9

397.5 (26/7)

234.2

72.65

47.3

2480

Code words are from the Aluminum Association Publication 50, 7th Edition, Table C20 (add " /  XLP " suffix for NS90)
NS75 with black LLDPE (optionally MDPE) insulation, 1/c printed, 1/c no marking
NS90 with black XLPE insulation, 1/c printed, 1/c no marking
Neutral support conductors 266.8 kcmil and larger are round wire ACSR, minimum Type 16, otherwise
Type 100 compact  ACSR conductors are used.
Overall diameter is the multiplex assembly circumscribing circle diameter


Triplex Unjacketed NS75/NS90 Reduced Neutral Electrical Data

Code
Word

Phase Size
(Stranding)
AWG/kcmil

Neutral
Size
(Stranding)
AWG/kcmil

Phase Conductor Resistance

Inductive
Reactance
(ohm/km)

Cable
Ampacity
(amps)

Rdc @ 20ºC
(ohm/km)

Rac @ 50ºC
(ohm/km)

Rac @ 75ºC
(ohm/km)

Rac @ 90ºC
(ohm/km)

NS75

NS90

Caesium

4 (7)

6 (6/1)

1.38

1.56

1.70

1.78

0.0991

105

125

Indium

2 (7)

4 (6/1)

0.865

0.979

1.07

1.12

0.0943

140

165

-

1 (7)

2 (6/1)

0.687

0.778

0.848

0.890

0.0979

160

190

Rubidium

1/0 (7)

2 (6/1)

0.544

0.616

0.672

0.705

0.0955

185

220

Titanium

2/0 (7)

1 (6/1)

0.432

0.489

0.533

0.559

0.0933

210

255

Palladium

3/0 (7)

1/0 (6/1)

0.343

0.388

0.423

0.444

0.0912

245

290

Strontium

4/0 (7)

2/0 (6/1)

0.271

0.307

0.335

0.352

0.0893

280

335

 -

266.8 (18)

3/0 (6/1)

0.215

0.244

0.268

0.282

0.0914

325

390

 -

336.4 (18)

4/0 (6/1)

0.171

0.193

0.215

0.225

0.0894

375

450

 -

397.5 (18)

266.8 (26/7)

0.144

0.164

0.184

0.193

0.0881

415

500

 -

477 (18)

336.4 (26/7)

0.121

0.136

0.155

0.163

0.0867

460

560

 -

500 (18)

397.5 (26/7)

0.115

0.130

0.149

0.156

0.0865

500

605

Rdc at 20°C is taken from CSA C49.5
Rac at 90°C is only applicable to NS90 cable
Ampacities are from the CE Code C22.1-06, Table 36A, based on 30°C ambient air,
0.6 m/s wind, and solar radiation of 1025 W/m²