Duplex Jacketed NS75/NS90 FT1 Secondary Distribution Cable
REFERENCES
Neutral Supported Cable
Standards
Description
Characteristics
Related Information
Standards
National  CSA C22.2 N° 129
Description

 
Nexans’ duplex neutral supported cables consist of an assembly of one insulated phase conductor factory-cabled around a neutral conductor. The neutral conductor is the supporting member. The conductors are insulated with polyethylene (PE) rated 75 °C or crosslinked polyethylene (XLPE) rated 90 °C.

 

Application

Neutral supported cables are intended for use either as a service drop cable between a power pole and the service entrance, or as a secondary distribution cable between poles. Their use is limited to circuits not exceeding 600 volts phase-to-phase.

Duplex service drop cables are intended to deliver single-phase power from the secondary power line or pole-mounted transformer to the service entrance conductors at the user’s building or other structures.  

Optional construction includes an insulated control/supply conductor.

 


 TOP
Characteristics
Construction characteristics
With smaller neutral conductor No  
Number of conductors 2  

 TOP
Duplex Jacketed NS75/NS90 FT1 Physical Data

Phase Conductor

Full  Size Neutral Support

Cable Assembly

Size
(Stranding)
AWG
or kcmil

Diameter
(mm)

Jacket
Diameter
(mm)

Size
(Stranding)
AWG
or kcmil

Area
(mm²)

Rated
Strength
(kN)

Overall
Diameter
(mm)

Total 
Weight
(kg/km)

6 (7)

4.29

8.2

6 (6/1)

15.48

5.20

12.8

135

4 (7)

5.41

9.3

4 (6/1)

24.71

8.14

15.1

196

2 (7)

6.81

10.7

2 (6/1)

39.23

12.41

18.1

291

1 (7)

7.59

13.1

1 (6/1)

49.48

15.48

21.3

393

1/0 (7)

8.53

14.0

1/0 (6/1)

62.39

19.08

23.3

478

2/0 (7)

9.55

15.0

2/0 (6/1)

78.65

23.80

25.4

583

3/0 (7)

10.74

16.2

3/0 (6/1)

99.23

29.67

27.9

714

4/0 (7)

12.07

17.5

4/0 (6/1)

125.1

37.45

30.7

879

266.8 (18)

13.64

20.2

266.8 (26/7)

157.2

50.10

36.4

1117

336.4 (18)

15.32

22.9

336.4 (26/7)

198.2

62.31

41.2

1427

397.5 (18)

16.74

24.3

397.5 (26/7)

234.2

72.65

44.2

1657

477 (18)

18.34

25.9

477 (26/7)

281.1

87.17

47.7

1951

500 (18)

18.69

26.2

500 (30/7)

312.5

109.40

49.2

2176

NS75 with black LLDPE (optionally MDPE) insulation, black PVC jacket
NS90 with black XLPE insulation, black PVC jacket
Neutral support conductors 266.8 kcmil and larger are round wire ACSR, minimum Type 16, otherwise
Type 100 compact ACSR conductors are used
Note: Only full neutral sizes are recommended for duplex cable assemblies
Overall diameter is the multiplex assembly circumscribing circle diameter


Duplex Jacketed NS75/NS90 FT1 Electrical Data

Phase Size
(Stranding)
AWG
ou kcmil

Phase Conductor Resistance

Inductive
Reactance
(ohm/km)

Cable Ampacity
(amps)

Rdc @ 20ºC
(ohm/km)

Rac @ 50ºC
(ohm/km)

Rac @ 75ºC
(ohm/km)

Rac @ 90ºC
(ohm/km)

NS75

NS90

6 (7)

2.19

2.48

2.70

2.84

0.1207

80

95

4 (7)

1.38

1.56

1.70

1.78

0.1129

105

125

2 (7)

0.865

0.979

1.07

1.12

0.1061

140

165

1 (7)

0.687

0.778

0.848

0.890

0.1129

160

190

1/0 (7)

0.544

0.616

0.672

0.705

0.1093

185

220

2/0 (7)

0.432

0.489

0.533

0.559

0.1061

210

255

3/0 (7)

0.343

0.388

0.423

0.444

0.1030

245

290

4/0 (7)

0.271

0.307

0.335

0.352

0.1001

280

335

266.8 (18)

0.215

0.244

0.268

0.282

0.1007

325

390

336.4 (18)

0.171

0.193

0.215

0.225

0.1015

375

450

397.5 (18)

0.144

0.164

0.184

0.193

0.0993

415

500

477 (18)

0.121

0.136

0.155

0.163

0.0973

460

560

500 (18)

0.115

0.130

0.149

0.156

0.0968

500

605

Rdc at 20°C is taken from CSA C49.5
Rac at 90°C is only applicable to NS90 cable
Ampacities are from the CE Code C22.1-06, Table 36A, based on 30°C ambient air,
0.6 m/s wind, and  solar radiation of 1025 W/m²