Send link to this page print Your Nexans contact on this page
CORFLEX® II RA90 Copper Conductors Copper CORFLEX® II RA90 (–40°C) XLPE 600 Volts 90°C
REFERENCES
CORFLEX® II RA90 Copper Conductors
Standards
Description
Characteristics
Selling delivery information
Related Information
Standards
National  CSA C22.2 N° 123-96
Description

Single or multi copper or compact ACM aluminum conductors with EXELENE* cross-linked polyethylene insulation (RW90 XLPE) enclosed in a liquid- and vapour-tight solid corrugated aluminum sheath. An overall sunlight resistant, low temperature, low acid gas and low flame spread (LAG/LFS) PVC jacket with FT4 and AG14 rating.
Unjacketed CORFLEX with FT4 and AG14 ratings is also available. 

Rated 600 volts. LEAD FREE and RoHS compliant.

CSA File #LL19376 Class 5812 01 - Cable
CSA File #LL19376 Class 5818 01 - Hazardous Location Cable Application

 

Application

For exposed and concealed wiring in dry or wet locations and where exposed to the weather.  Nexans cables are marked "SUN RES" for sunlight resistant.
For use in ventilated, non-ventilated, and ladder type cabletroughs and ventilated flexible cableways in dry or wet locations.
For direct earth burial (with protection as required by Inspection Authority). For direct embedding in concrete, masonry or plaster (with permission as required by Local Inspection Authority).
For service entrance above or below ground.
CORFLEX® cable is certified for use in hazardous locations with approved connectors. Nexans Canada Type W connector are approved for Class II Divisions 1 and 2 (Groups E, F and G) and Class III Divisions 1 and 2.







Related documents
  Single conductor cables in free air  (279.5kb)
  Single conductor Copper cable direct buried ampacity table  (109.8kb)
  3 conductor Copper cable direct buried ampacity table  (139.6kb)



 TOP
Characteristics
Construction characteristics
Conductor material Copper  
Electrical characteristics
Maximum operating voltage 600V  
Usage characteristics
Maximum operating temperature 90°C  

 TOP
Single Copper Conductor

Size AWG
or
kcmil

Approximate Diameter

Approx Net Cable Weight

Connectors
(Nexans
Catalogue No)

Minimum†
Bending
Radius

Ampacity
30°C
Ambient
(amps)
(CE Code 
Table 1)**

Over Sheath

Over PVC
Jacket

Without Jacket

With PVC
jacket

mm

in

mm

in

kg/km

lbs/kft

kg/km

lbs/kft

Dry
Location
Type D

Wet
Hazardous
Location
Type W

mm

in

1

15.7

0.62

18.3

0.72

510

342

626

421

16D2

16W2

192

7.6

210

1/0

16.3

0.64

18.9

0.75

623

419

737

496

16D2

16W2

198

7.8

245

2/0

19.6

0.77

22.4

0.88

804

540

930

625

20D3

20W3

235

9.3

285

3/0

20.2

0.79

22.9

0.90

972

653

1107

744

20D3

20W3

240

9.5

330

4/0

21.1

0.83

23.7

0.93

1190

800

1320

887

20D3

20W3

249

9.8

385

250

23.8

0.94

26.4

1.04

1406

945

1562

1050

25D3

25W3

277

10.9

425

300

25.1

0.99

27.7

1.09

1640

1102

1801

1210

25D3

25W3

291

11.5

480

350

25.9

1.02

28.9

1.14

1870

1256

2052

1380

25D3

25W3

303

11.9

530

400

29.7

1.17

32.3

1.27

2208

1484

2396

1610

30D4

30W4

339

13.4

575

500

30.9

1.22

33.8

1.34

2690

1807

2895

1945

30D4

30W4

355

14.0

660

600

35.1

1.38

37.6

1.48

3246

2181

3467

2330

35D5

35W5

395

15.5

740

750

38.9

1.53

41.7

1.64

4044

2717

4293

2885

40D5

40W5

438

17.2

845

1000

42.4

1.67

45.2

1.78

5273

3543

5543

3725

45D6

45W6

475

18.7

1000


Two Copper Conductors

Size AWG
or
kcmil

Approximate Diameter

Approx Net Cable Weight

Connectors
(Nexans
Catalogue No)

Minimum†
Bending
Radius

Ampacity
30°C
Ambient
(amps)
(CE Code 
Table 2**)

Over Sheath

Over PVC
Jacket

Without Jacket

With PVC
jacket

mm

in

mm

in

kg/km

lbs/kft

kg/km

lbs/kft

Dry
Location
Type D

Wet
Hazardous
Location
Type W

mm

in

14

11.9

0.47

14.7

0.58

126

85

134

90

13D2

13W2

154

6.1

15

12

13.0

0.51

15.7

0.62

164

110

238

160

13D2

13W2

165

6.5

20

10

14.0

0.55

17.0

0.67

201

135

283

190

13D2

13W2

178

7.0

30

8

19.2

0.76

21.8

0.86

324

218

446

300

20D3

20W3

229

9.0

45

6

20.1

0.79

22.6

0.89

422

283

551

370

20D3

20W3

237

9.3

65

4

23.4

0.92

26.2

1.03

609

409

759

510

25D3

25W3

275

10.8

85

3

24.4

0.96

26.9

1.06

715

480

871

585

25D3

25W3

282

11.1

105

2

25.4

1.00

27.9

1.10

850

571

1012

680

25D3

25W3

293

11.5

120

1

29.4

1.16

32.0

1.26

1069

719

1314

883

30D4

30W4

336

13.2

140

1/0

33.1

1.32

36.2

1.42

1387

932

1600

1075

35D5

35W5

380

15.0

155

2/0

35.2

1.37

37.7

1.48

1651

1109

1871

1257

35D5

35W5

396

15.6

185

3/0

39.0

1.53

41.8

1.64

2072

1392

2320

1560

40D5

40W5

439

17.3

210

4/0

40.8

1.60

43.6

1.71

2488

1672

2747

1846

40D5

40W5

458

18.0

235

250

44.5

1.75

47.0

1.85

3117

2095

3400

2285

45D6

45W6

494

19.4

265

300

48.5

1.91

51.3

2.02

3694

2482

4003

2690

50D8

50W8

539

21.2

295


Three Copper Conductors

Size AWG
or
kcmil

Approximate Diameter

Approx Net Cable Weight

Connectors
(Nexans
Catalogue No)

Minimum†
Bending
Radius

Ampacity
30°C
Ambient
(amps)
(CE Code 
Table 2)***

Over Sheath

Over PVC
Jacket

Without Jacket

With PVC
jacket

mm

in

mm

in

kg/km

lbs/kft

kg/km

lbs/kft

Dry
Location
Type D

Wet
Hazardous
Location
Type W

mm

in

14

12.4

0.49

15.5

0.61

164

110

238

160

13D2

13W2

163

6.4

15

12

13.5

0.53

16.5

0.65

201

135

283

190

13D2

13W2

173

6.8

20

10 

15.2

0.60

18.3

0.72

290

195

379

255

16D2

16W2

192

7.6

30

8

19.6

0.77

22.6

0.89

439

295

551

370

20D3

20W3

237

9.3

45

6

20.8

0.82

23.4

0.92

567

381

699

470

20D3

20W3

246

9.7

65

24.1

0.95

26.9

1.06

834

561

990

665

25D3

25W3

282

11.1

85

25.1

0.99

27.9

1.10

992

667

1153

775

25D3

25W3

293

11.5

105

29.2

1.15

31.8

1.25

1281

861

1466

985

30D4

30W4

334

13.1

120

30.7

1.21

33.4

1.31

1663

1117

1751

1177

30D4

30W4

351

13.8

140

1/0

34.3

1.35

37.1

1.46

1898

1275

2115

1421

35D5

35W5

390

15.3

155

2/0

38.9

1.43

42.0

1.53

2398

1611

2644

1777

40D5

40W5

441

17.4

185††

3/0

40.2

1.58

43.4

1.71

2873

1931

3128

2102

40D5

40W5

456

17.9

210

4/0

43.5

1.71

45.9

1.81

3569

2398

3845

2584

45D6

45W6

482

19.0

235

250

48.5

1.91

51.3

2.02

4394

2952

4703

3160

50D8

50W8

539

21.2

265


Four Copper Conductors

Size AWG
or
kcmil

Approximate Diameter

Approx Net Cable Weight

Connectors
(Nexans
Catalogue No)

Minimum†
Bending
Radius

Ampacity
30°C
Ambient
(amps)
(CE Code 
Table 2)***

Over Sheath

Over PVC
Jacket

Without Jacket

With PVC
jacket

mm

in

mm

in

kg/km

lbs/kft

kg/km

lbs/kft

Dry
Location
Type D

Wet
Hazardous
Location
Type W

mm

in

14

13.3

0.53

16.3

0.64

195

130

270

180

13D2

13W2

171

6.7

15

12 

15.1

0.59

18.1

0.71

275

185

360

240

16D2

16W2

190

7.5

20

10 

16.0

0.63

19.0

0.75

350

235

445

300

16D2

16W2

200

7.9

30

8

20.6

0.81

23.6

0.93

536

360

655

440

20D3

20W3

248

9.8

45

23.9

0.94

26.4

1.04

770

517

923

620

25D3

25W3

277

10.9

65

25.7

1.01

28.2

1.11

1086

730

1250

840

25D3

25W3

296

11.7

85

29.7

1.17

32.3

1.27

1397

939

1585

1065

30D4

30W4

339

13.4

105

33.0

1.30

36.1

1.42

1741

1170

1949

1310

35D5

35W5

379

14.9

120

34.4

1.36

37.1

1.46

2158

1450

2272

1530

35D5

35W5

390

15.3

140

1/0 

40.0

1.57

42.4

1.67

2654

1783

2909

1955

40D5

40W5

445

17.5

155

2/0 

40.6

1.60

43.2

1.70

3207

2155

3202

2152

40D5

40W5

454

17.9

185††

3/0 

43.9

1.73

46.7

1.84

3874

2603

4155

2792

45D6

45W6

490

19.3

210

4/0 

49.7

1.96

52.5

2.07

4934

3315

5252

3529

50D8

50W8

551

21.7

235


 TOP
Selling delivery information
Insulation Colour Code:
1 Conductor - Black
2 Conductor - Black, White #14 - #2
3 Conductors - Black, Red, White #14 - #2
4 Conductors - Black, Red, Blue, White #14 - #2
Black Insulation with white printed numbers #1 and larger

* Registered Trademark of Nexans Canada Inc.

***Assuming 4th conductor is the neutral of a balanced 3-phase 4 wire system.
#C.E. Code Rule 12-712(3)
††For 3 wire 120/240 and 120/208 volt residential services or sub-services, the ampacity for #2/0 AWG copper is 200 amperes. In this case the 5% adjustment per C.E. Code Rule 8-106(1) cannot be applied.

   Single conductor cables in free air (279 kB)
   Single conductor Copper cable direct buried ampacity table (109 kB)
   3 conductor Copper cable direct buried ampacity table (139 kB)



Nexans © copyright 2001 - 2012   Legal Notice | Contact Us | Site Map