Description
Standards
National : CSA C22.2 N° 123-96Description
Single or multi copper or compact ACM aluminum conductors with EXELENE* cross-linked polyethylene insulation (RW90 XLPE) enclosed in a liquid- and vapour-tight solid corrugated aluminum sheath. An overall sunlight resistant, low temperature, low acid gas and low flame spread (LAG/LFS) PVC jacket with FT4 and AG14 rating.
Unjacketed CORFLEX with FT4 and AG14 ratings is also available.
Rated 600 volts. LEAD FREE and RoHS compliant.
CSA File #LL19376 Class 5812 01 - Cable
CSA File #LL19376 Class 5818 01 - Hazardous Location Cable Application
Application
For exposed and concealed wiring in dry or wet locations and where exposed to the weather. Nexans cables are marked "SUN RES" for sunlight resistant.
For use in ventilated, non-ventilated, and ladder type cabletroughs and ventilated flexible cableways in dry or wet locations.
For direct earth burial (with protection as required by Inspection Authority). For direct embedding in concrete, masonry or plaster (with permission as required by Local Inspection Authority).
For service entrance above or below ground.
CORFLEX® cable is certified for use in hazardous locations with approved connectors. Nexans Canada Type W connector are approved for Class II Divisions 1 and 2 (Groups E, F and G) and Class III Divisions 1 and 2.
Characteristics
| Construction characteristics | |
|---|---|
| Conductor material | Copper |
| Electrical characteristics | |
| Maximum operating voltage | 600V |
| Usage characteristics | |
| Maximum operating temperature | 90°C |
Docs and info
Single Copper Conductor
|
Size AWG |
Approximate Diameter |
Approx Net Cable Weight |
Connectors |
Minimum† |
Ampacity |
||||||||
|
Over Sheath |
Over PVC |
Without Jacket |
With PVC |
||||||||||
|
mm |
in |
mm |
in |
kg/km |
lbs/kft |
kg/km |
lbs/kft |
Dry |
Wet |
mm |
in |
||
|
1 |
15.7 |
0.62 |
18.3 |
0.72 |
510 |
342 |
626 |
421 |
16D2 |
16W2 |
192 |
7.6 |
210 |
|
1/0 |
16.3 |
0.64 |
18.9 |
0.75 |
623 |
419 |
737 |
496 |
16D2 |
16W2 |
198 |
7.8 |
245 |
|
2/0 |
19.6 |
0.77 |
22.4 |
0.88 |
804 |
540 |
930 |
625 |
20D3 |
20W3 |
235 |
9.3 |
285 |
|
3/0 |
20.2 |
0.79 |
22.9 |
0.90 |
972 |
653 |
1107 |
744 |
20D3 |
20W3 |
240 |
9.5 |
330 |
|
4/0 |
21.1 |
0.83 |
23.7 |
0.93 |
1190 |
800 |
1320 |
887 |
20D3 |
20W3 |
249 |
9.8 |
385 |
|
250 |
23.8 |
0.94 |
26.4 |
1.04 |
1406 |
945 |
1562 |
1050 |
25D3 |
25W3 |
277 |
10.9 |
425 |
|
300 |
25.1 |
0.99 |
27.7 |
1.09 |
1640 |
1102 |
1801 |
1210 |
25D3 |
25W3 |
291 |
11.5 |
480 |
|
350 |
25.9 |
1.02 |
28.9 |
1.14 |
1870 |
1256 |
2052 |
1380 |
25D3 |
25W3 |
303 |
11.9 |
530 |
|
400 |
29.7 |
1.17 |
32.3 |
1.27 |
2208 |
1484 |
2396 |
1610 |
30D4 |
30W4 |
339 |
13.4 |
575 |
|
500 |
30.9 |
1.22 |
33.8 |
1.34 |
2690 |
1807 |
2895 |
1945 |
30D4 |
30W4 |
355 |
14.0 |
660 |
|
600 |
35.1 |
1.38 |
37.6 |
1.48 |
3246 |
2181 |
3467 |
2330 |
35D5 |
35W5 |
395 |
15.5 |
740 |
|
750 |
38.9 |
1.53 |
41.7 |
1.64 |
4044 |
2717 |
4293 |
2885 |
40D5 |
40W5 |
438 |
17.2 |
845 |
|
1000 |
42.4 |
1.67 |
45.2 |
1.78 |
5273 |
3543 |
5543 |
3725 |
45D6 |
45W6 |
475 |
18.7 |
1000 |
Two Copper Conductors
|
Size AWG |
Approximate Diameter |
Approx Net Cable Weight |
Connectors |
Minimum† |
Ampacity |
||||||||
|
Over Sheath |
Over PVC |
Without Jacket |
With PVC |
||||||||||
|
mm |
in |
mm |
in |
kg/km |
lbs/kft |
kg/km |
lbs/kft |
Dry |
Wet |
mm |
in |
||
|
14 |
11.9 |
0.47 |
14.7 |
0.58 |
126 |
85 |
134 |
90 |
13D2 |
13W2 |
154 |
6.1 |
15 |
|
12 |
13.0 |
0.51 |
15.7 |
0.62 |
164 |
110 |
238 |
160 |
13D2 |
13W2 |
165 |
6.5 |
20 |
|
10 |
14.0 |
0.55 |
17.0 |
0.67 |
201 |
135 |
283 |
190 |
13D2 |
13W2 |
178 |
7.0 |
30 |
|
8 |
19.2 |
0.76 |
21.8 |
0.86 |
324 |
218 |
446 |
300 |
20D3 |
20W3 |
229 |
9.0 |
45 |
|
6 |
20.1 |
0.79 |
22.6 |
0.89 |
422 |
283 |
551 |
370 |
20D3 |
20W3 |
237 |
9.3 |
65 |
|
4 |
23.4 |
0.92 |
26.2 |
1.03 |
609 |
409 |
759 |
510 |
25D3 |
25W3 |
275 |
10.8 |
85 |
|
3 |
24.4 |
0.96 |
26.9 |
1.06 |
715 |
480 |
871 |
585 |
25D3 |
25W3 |
282 |
11.1 |
105 |
|
2 |
25.4 |
1.00 |
27.9 |
1.10 |
850 |
571 |
1012 |
680 |
25D3 |
25W3 |
293 |
11.5 |
120 |
|
1 |
29.4 |
1.16 |
32.0 |
1.26 |
1069 |
719 |
1314 |
883 |
30D4 |
30W4 |
336 |
13.2 |
140 |
|
1/0 |
33.1 |
1.32 |
36.2 |
1.42 |
1387 |
932 |
1600 |
1075 |
35D5 |
35W5 |
380 |
15.0 |
155 |
|
2/0 |
35.2 |
1.37 |
37.7 |
1.48 |
1651 |
1109 |
1871 |
1257 |
35D5 |
35W5 |
396 |
15.6 |
185 |
|
3/0 |
39.0 |
1.53 |
41.8 |
1.64 |
2072 |
1392 |
2320 |
1560 |
40D5 |
40W5 |
439 |
17.3 |
210 |
|
4/0 |
40.8 |
1.60 |
43.6 |
1.71 |
2488 |
1672 |
2747 |
1846 |
40D5 |
40W5 |
458 |
18.0 |
235 |
|
250 |
44.5 |
1.75 |
47.0 |
1.85 |
3117 |
2095 |
3400 |
2285 |
45D6 |
45W6 |
494 |
19.4 |
265 |
|
300 |
48.5 |
1.91 |
51.3 |
2.02 |
3694 |
2482 |
4003 |
2690 |
50D8 |
50W8 |
539 |
21.2 |
295 |
Three Copper Conductors
|
Size AWG |
Approximate Diameter |
Approx Net Cable Weight |
Connectors |
Minimum† |
Ampacity |
||||||||
|
Over Sheath |
Over PVC |
Without Jacket |
With PVC |
||||||||||
|
mm |
in |
mm |
in |
kg/km |
lbs/kft |
kg/km |
lbs/kft |
Dry |
Wet |
mm |
in |
||
|
14 |
12.4 |
0.49 |
15.5 |
0.61 |
164 |
110 |
238 |
160 |
13D2 |
13W2 |
163 |
6.4 |
15 |
|
12 |
13.5 |
0.53 |
16.5 |
0.65 |
201 |
135 |
283 |
190 |
13D2 |
13W2 |
173 |
6.8 |
20 |
|
10 |
15.2 |
0.60 |
18.3 |
0.72 |
290 |
195 |
379 |
255 |
16D2 |
16W2 |
192 |
7.6 |
30 |
|
8 |
19.6 |
0.77 |
22.6 |
0.89 |
439 |
295 |
551 |
370 |
20D3 |
20W3 |
237 |
9.3 |
45 |
|
6 |
20.8 |
0.82 |
23.4 |
0.92 |
567 |
381 |
699 |
470 |
20D3 |
20W3 |
246 |
9.7 |
65 |
|
4 |
24.1 |
0.95 |
26.9 |
1.06 |
834 |
561 |
990 |
665 |
25D3 |
25W3 |
282 |
11.1 |
85 |
|
3 |
25.1 |
0.99 |
27.9 |
1.10 |
992 |
667 |
1153 |
775 |
25D3 |
25W3 |
293 |
11.5 |
105 |
|
2 |
29.2 |
1.15 |
31.8 |
1.25 |
1281 |
861 |
1466 |
985 |
30D4 |
30W4 |
334 |
13.1 |
120 |
|
1 |
30.7 |
1.21 |
33.4 |
1.31 |
1663 |
1117 |
1751 |
1177 |
30D4 |
30W4 |
351 |
13.8 |
140 |
|
1/0 |
34.3 |
1.35 |
37.1 |
1.46 |
1898 |
1275 |
2115 |
1421 |
35D5 |
35W5 |
390 |
15.3 |
155 |
|
2/0 |
38.9 |
1.43 |
42.0 |
1.53 |
2398 |
1611 |
2644 |
1777 |
40D5 |
40W5 |
441 |
17.4 |
185†† |
|
3/0 |
40.2 |
1.58 |
43.4 |
1.71 |
2873 |
1931 |
3128 |
2102 |
40D5 |
40W5 |
456 |
17.9 |
210 |
|
4/0 |
43.5 |
1.71 |
45.9 |
1.81 |
3569 |
2398 |
3845 |
2584 |
45D6 |
45W6 |
482 |
19.0 |
235 |
|
250 |
48.5 |
1.91 |
51.3 |
2.02 |
4394 |
2952 |
4703 |
3160 |
50D8 |
50W8 |
539 |
21.2 |
265 |
Four Copper Conductors
|
Size AWG |
Approximate Diameter |
Approx Net Cable Weight |
Connectors |
Minimum† |
Ampacity |
||||||||
|
Over Sheath |
Over PVC |
Without Jacket |
With PVC |
||||||||||
|
mm |
in |
mm |
in |
kg/km |
lbs/kft |
kg/km |
lbs/kft |
Dry |
Wet |
mm |
in |
||
|
14 |
13.3 |
0.53 |
16.3 |
0.64 |
195 |
130 |
270 |
180 |
13D2 |
13W2 |
171 |
6.7 |
15 |
|
12 |
15.1 |
0.59 |
18.1 |
0.71 |
275 |
185 |
360 |
240 |
16D2 |
16W2 |
190 |
7.5 |
20 |
|
10 |
16.0 |
0.63 |
19.0 |
0.75 |
350 |
235 |
445 |
300 |
16D2 |
16W2 |
200 |
7.9 |
30 |
|
8 |
20.6 |
0.81 |
23.6 |
0.93 |
536 |
360 |
655 |
440 |
20D3 |
20W3 |
248 |
9.8 |
45 |
|
6 |
23.9 |
0.94 |
26.4 |
1.04 |
770 |
517 |
923 |
620 |
25D3 |
25W3 |
277 |
10.9 |
65 |
|
4 |
25.7 |
1.01 |
28.2 |
1.11 |
1086 |
730 |
1250 |
840 |
25D3 |
25W3 |
296 |
11.7 |
85 |
|
3 |
29.7 |
1.17 |
32.3 |
1.27 |
1397 |
939 |
1585 |
1065 |
30D4 |
30W4 |
339 |
13.4 |
105 |
|
2 |
33.0 |
1.30 |
36.1 |
1.42 |
1741 |
1170 |
1949 |
1310 |
35D5 |
35W5 |
379 |
14.9 |
120 |
|
1 |
34.4 |
1.36 |
37.1 |
1.46 |
2158 |
1450 |
2272 |
1530 |
35D5 |
35W5 |
390 |
15.3 |
140 |
|
1/0 |
40.0 |
1.57 |
42.4 |
1.67 |
2654 |
1783 |
2909 |
1955 |
40D5 |
40W5 |
445 |
17.5 |
155 |
|
2/0 |
40.6 |
1.60 |
43.2 |
1.70 |
3207 |
2155 |
3202 |
2152 |
40D5 |
40W5 |
454 |
17.9 |
185†† |
|
3/0 |
43.9 |
1.73 |
46.7 |
1.84 |
3874 |
2603 |
4155 |
2792 |
45D6 |
45W6 |
490 |
19.3 |
210 |
|
4/0 |
49.7 |
1.96 |
52.5 |
2.07 |
4934 |
3315 |
5252 |
3529 |
50D8 |
50W8 |
551 |
21.7 |
235 |
Related documents
Selling information
1 Conductor - Black
2 Conductor - Black, White #14 - #2
3 Conductors - Black, Red, White #14 - #2
4 Conductors - Black, Red, Blue, White #14 - #2
Black Insulation with white printed numbers #1 and larger
* Registered Trademark of Nexans Canada Inc.