ENERGEX® CN 25 kV 133% Al 1/3 Neutral (UD)

Send link to this page print Your Nexans contact on this page
ENERGEX® CN 25 kV 133% Al 1/3 Neutral (UD) CN Primary Distribution Cables 5 to 46 kV
REFERENCES
ENERGEX® CN
Standards
Description
Characteristics
Selling delivery information
Related Information
Standards
National  CSA C68.5
Description

Nexans ENERGEX® CN Distribution Cables are single conductor concentric neutral power cables available in voltage classes from 5 kV to 46 kV.  These cables are manufactured using the latest in clean compound handling technology.  ENERGEX CN has a semiconducting crosslinked polyolefin (XLPO) conductor shield, a tree retardant crosslinked polyethylene (TRXLPE) insulation and a strippable semiconducting crosslinked polyolefin (XLPO) insulation shield.  Three phase systems typically use CN cables with 1/3 neutrals. 

These cables are LEAD FREE and RoHS compliant. 

 


Application

ENERGEX® CN Distribution Cables are suitable for use above ground in open air, in cable tray, in conduit in air, aerially when suspended on a messenger wire, and either directly buried or in duct. ENERGEX® CN cables are suitable for continuous operation at 90ºC wet or dry, and are sunlight resistant.



Related documents
  CN Reduced Neutral Design Options  (24.2kb)
  Concentric Neutral Insulation System  (60.8kb)
  Concentric Neutral Jacket Thickness & Test Voltage  (20.7kb)
  Concentric Neutral Installation  (23.1kb)
  Concentric Neutral Field Testing  (85.6kb)



 TOP
Characteristics
Construction characteristics
Conductor material Aluminium  
Electrical characteristics
Operating voltage 25kV  

 TOP
CN 25 kV 133% Al 1/3 Neutral (UD) Physical Data

Conductor
Size

Stranding
(No of
Wires)

Insulation
Diameter

Concentric
Neutral*

Minimum
Jacket
Thickness
(mm)

Approx
Jacket
Diameter
(mm)

Approx
Cable
Weight
(kg/km)

AWG/
kcmil

mm²

Nom
(mm)

No of
Wires

AWG

 

 

 

 

 

 

 

 

 

1

42.4

solid

24.7

6

14

1.14

32.5

1012

1

42.4

18

25.0

6

14

1.14

32.8

1027

 

 

 

 

 

 

 

 

 

1/0

53.5

solid

25.6

6

14

1.14

33.4

1079

1/0

53.5

18

25.8

6

14

1.14

33.7

1094

 

 

 

 

 

 

 

 

 

2/0

67.4

18

26.9

7

14

1.14

34.7

1198

3/0

85.0

18

28.1

9

14

1.14

36.4

1369

4/0

107

18

29.4

11

14

1.14

37.7

1525

 

 

 

 

 

 

 

 

 

250

127

35

30.7

13

14

1.14

39.1

1808

300

152

35

32.0

15

14

1.14

40.3

2002

350

177

35

33.2

18

14

1.14

41.5

2202

400

203

35

34.3

20

14

1.78

44.0

2493

 

 

 

 

 

 

 

 

 

500

253

35

36.3

25

14

1.78

46.0

2865

600

304

58

38.5

19

12

1.78

49.1

3333

750

380

58

40.9

24

12

1.78

52.3

3973

1000

507

58

44.7

20

10

1.78

57.1

4985

* The number of wires is increased where necessary to comply with the CSA 7.0 mm maximum 
   CN wire-to-wire spacing limit.


CN 25 kV 133% Al 1/3 Neutral (UD) Electrical Data

Conductor
Size

Stranding
(No of
Wires)

DC
Resistance
20°C
(Ω/km)

AC***
Resistance
90°C
(Ω/km,
60 Hz)

Inductive
Reactance***
(Ω/km,
60 Hz)

Capacitance
(µF/km)

Capacitive
Reactance
(MΩ∙km,
60 Hz)

AWG/
kcmil

mm²

1

42.4

solid

0.6664

0.8545

0.3406

0.1156

23000

1

42.4

18

0.6798

0.8716

0.3317

0.1178

22500

 

 

 

 

 

 

 

 

1/0

53.5

solid

0.5282

0.6773

0.3406

0.1237

21500

1/0

53.5

18

0.5388

0.6909

0.3230

0.1262

21000

 

 

 

 

 

 

 

 

2/0

67.4

18

0.4275

0.5482

0.3145

0.1349

19700

3/0

85.0

18

0.3391

0.4350

0.3055

0.1453

18300

4/0

107

18

0.2689

0.3450

0.2968

0.1558

17000

 

 

 

 

 

 

 

 

250

127

35

0.2275

0.2921

0.2900

0.1674

15800

300

152

35

0.1897

0.2436

0.2831

0.1778

14900

350

177

35

0.1626

0.2090

0.2772

0.1864

14200

400

203

35

0.1422

0.1830

0.2721

0.1958

13500

 

 

 

 

 

 

 

 

500

253

35

0.1138

0.1467

0.2638

0.2107

12600

600

304

58

0.0948

0.1225

0.2563

0.2277

11600

750

380

58

0.0759

0.0985

0.2480

0.2465

10800

1000

507

58

0.0569

0.0745

0.2362

0.2770

9600

*** AC resistance, including skin effect, and inductive reactance are calculated 
for cables in separate ducts, or spaced in air or direct burial for 1/3 CN. 
Assumed spacing is 190 mm flat axial separation. Balanced three-phase 
current loading is assumed for 1/3 CN cables.


 TOP
Selling delivery information

For Energex Conductor Data click here.

For Energex Component Thicknesses click here.


   CN Reduced Neutral Design Options (24 kB)
   Concentric Neutral Insulation System (60 kB)
   Concentric Neutral Jacket Thickness & Test Voltage (20 kB)
   Concentric Neutral Installation (23 kB)
   Concentric Neutral Field Testing (85 kB)