français Login Get Registered Catalog Browser Contact Us
Nexans Canada Worldwide Leader of Electrical Cables

About Nexans

Products and Solutions

Customer Service

Work at Nexans

News and Press

Go

ENERGEX® CN 15 kV 100% Al Full Neutral (URD)

Send link to this page print Your Nexans contact on this page
ENERGEX® CN 15 kV 100% Al Full Neutral (URD)  CN Primary Distribution Cables 15 to 46 KV
REFERENCES
ENERGEX® CN
Standards
Description
Characteristics
Related Information
Standards
National  CSA C68.5
Description

Nexans ENERGEX® CN Distribution Cables are single conductor concentric neutral power cables available in voltage classes from 15 kV to 46 kV.  These cables are manufactured using the latest in clean compound handling technology.  ENERGEX® CN has a semiconducting crosslinked polyolefin (XLPO) conductor shield, a tree retardant crosslinked polyethylene (TRXLPE) insulation and a strippable semiconducting crosslinked polyolefin (XLPO) insulation shield.  For single phase systems the conductance of the neutral is equivalent to that of the phase conductor. 

These cables are LEAD FREE and RoHS compliant. 

 


Application

ENERGEX® CN Distribution Cables are suitable for use above ground in open air, in conduit in air, directly buried, in underground duct, or aerially when suspended on a messenger wire.   While suitable for use in cable tray in a typical Utility installation, ENERGEX® CN is not TC rated and cannot be used in cable tray in an installation subject to the requirements of the Canadian Electrical Code.  ENERGEX®  CN cables are suitable for continuous operation at 90ºC wet or dry, and are sunlight resistant.



Related documents
  Concentric Neutral Design Options  (24.2kb)
  Concentric Neutral Insulation System   (60.8kb)
  Concentric Neutral Jacket Thickness & Test Voltage  (20.7kb)
  Concentric Neutral Installation  (23.1kb)
  Concentric Neutral Field Testing  (85.6kb)



 TOP
Characteristics
Construction characteristics
Conductor material Aluminium  
With smaller neutral conductor No  
Electrical characteristics
Operating voltage 15kV  

 TOP
CN 15 kV 100% Al Full Neutral (URD) Physical Data

Conductor
Size

Stranding
(No of
Wires)

Insulation
Diameter

Concentric
Neutral*

Minimum
Jacket
Thickness
(mm)

Approx
Jacket
Diameter
(mm)

Approx
Cable
Weight
(kg/km)

AWG/
kcmil

mm²

Nom
(mm)

No of
Wires

AWG

 

 

 

 

 

 

 

 

 

2

33.6

solid

16.6

10

14

1.14

24.4

714

2

33.6

7

16.8

10

14

1.14

24.7

722

 

 

 

 

 

 

 

 

 

1

42.4

solid

17.4

13

14

1.14

25.2

811

1

42.4

18

17.7

13

14

1.14

25.5

826

 

 

 

 

 

 

 

 

 

1/0

53.5

solid

18.3

16

14

1.14

26.1

915

1/0

53.5

18

18.6

16

14

1.14

26.4

938

 

 

 

 

 

 

 

 

 

2/0

67.4

18

19.6

20

14

1.14

27.4

1071

3/0

85.0

18

20.8

16

12

1.14

29.4

1287

4/0

107

18

22.1

20

12

1.14

30.8

1503

 

 

 

 

 

 

 

 

 

250

127

35

23.4

16

10

1.14

33.2

1949

300

152

35

24.7

18

10

1.14

34.4

2180

350

177

35

25.9

20

10

1.14

35.7

2403

* The number of wires is increased where necessary to comply with the CSA 7.0 mm maximum 
   CN wire-to-wire spacing limit.


CN 15 kV 100% Al Full Neutral (URD) Electrical Data

Size

Stranding
(No of
Wires)

DC
Resistance
20°C
(Ω/km)

AC***
Resistance
90°C
(Ω/km,
60 Hz)

Inductive
Reactance***
(Ω/km,
60 Hz)

Capacitance
(µF/km)

Capacitive
Reactance
(MΩ∙km,
60 Hz)

AWG/
kcmil

mm²

 

 

 

 

 

 

 

 

2

33.6

solid

0.8407

1.0779

0.2419

0.1559

17000

2

33.6

7

0.8575

1.0994

0.2409

0.1596

16600

 

 

 

 

 

 

 

 

1

42.4

solid

0.6664

0.8545

0.2390

0.1675

15800

1

42.4

18

0.6798

0.8716

0.2380

0.1711

15500

 

 

 

 

 

 

 

 

1/0

53.5

solid

0.5282

0.6773

0.2357

0.1808

14700

1/0

53.5

18

0.5388

0.6909

0.2348

0.1851

14300

 

 

 

 

 

 

 

 

2/0

67.4

18

0.4275

0.5482

0.2313

0.1994

13300

3/0

85.0

18

0.3391

0.4350

0.2258

0.2146

12400

4/0

107

18

0.2689

0.3450

0.2219

0.2337

11400

 

 

 

 

 

 

 

 

250

127

35

0.2275

0.2921

0.2164

0.2527

10500

300

152

35

0.1897

0.2436

0.2129

0.2698

9800

350

177

35

0.1626

0.2090

0.2100

0.2861

9300

*** AC resistance, including skin effect, and inductive reactance are calculated 
for one isolated cable in duct, or in air or direct burial.


 TOP
   Concentric Neutral Design Options (24 kB)
   Concentric Neutral Insulation System  (60 kB)
   Concentric Neutral Jacket Thickness & Test Voltage (20 kB)
   Concentric Neutral Installation (23 kB)
   Concentric Neutral Field Testing (85 kB)



Nexans © copyright 2001 - 2012   Legal Notice | Contact Us | Site Map