français Login Get Registered Catalog Browser Contact Us
Nexans Canada Worldwide Leader of Electrical Cables

About Nexans

Products and Solutions

Customer Service

Work at Nexans

News and Press

Go

ENERGEX® CN 15 kV 133% Al Full Neutral (URD)

Send link to this page print Your Nexans contact on this page
ENERGEX® CN 15 kV 133% Al Full Neutral (URD) CN Primary Distribution Cables 15 to 46 KV
REFERENCES
ENERGEX® CN
Standards
Description
Characteristics
Related Information
Standards
National  CSA C68.5
Description

Nexans ENERGEX® CN Distribution Cables are single conductor concentric neutral power cables available in voltage classes from 15 kV to 46 kV.  These cables are manufactured using the latest in clean compound handling technology.  ENERGEX® CN has a semiconducting crosslinked polyolefin (XLPO) conductor shield, a tree retardant crosslinked polyethylene (TRXLPE) insulation and a strippable semiconducting crosslinked polyolefin (XLPO) insulation shield.  For single phase systems the conductance of the neutral is equivalent to that of the phase conductor. 

These cables are LEAD FREE and RoHS compliant. 

 


Application

ENERGEX® CN Distribution Cables are suitable for use above ground in open air, in conduit in air, directly buried, in underground duct, or aerially when suspended on a messenger wire.   While suitable for use in cable tray in a typical Utility installation, ENERGEX® CN is not TC rated and cannot be used in cable tray in an installation subject to the requirements of the Canadian Electrical Code.  ENERGEX®  CN cables are suitable for continuous operation at 90ºC wet or dry, and are sunlight resistant.



Related documents
  Concentric Neutral Design Options  (24.2kb)
  Concentric Neutral Insulation System   (60.8kb)
  Concentric Neutral Jacket Thickness & Test Voltage  (20.7kb)
  Concentric Neutral Installation  (23.1kb)
  Concentric Neutral Field Testing  (85.6kb)



 TOP
Characteristics
Construction characteristics
Conductor material Aluminium  
With smaller neutral conductor No  
Electrical characteristics
Operating voltage 15kV  

 TOP
CN 15 kV 133% Al Full Neutral (URD) Physical Data

Conductor
Size

Stranding
(No of
Wires)

Insulation
Diameter

Concentric
Neutral*

Minimum
Jacket
Thickness
(mm)

Approx
Jacket
Diameter
(mm)

Approx
Cable
Weight
(kg/km)

AWG/
kcmil

mm²

Nom
(mm)

No of
Wires

AWG

 

 

 

 

 

 

 

 

 

2

33.6

solid

18.9

10

14

1.14

26.8

804

2

33.6

7

19.2

10

14

1.14

27.0

818

 

 

 

 

 

 

 

 

 

1

42.4

solid

19.7

13

14

1.14

27.6

900

1

42.4

18

20.0

13

14

1.14

27.8

915

 

 

 

 

 

 

 

 

 

1/0

53.5

solid

20.6

16

14

1.14

28.5

1012

1/0

53.5

18

20.9

16

14

1.14

28.7

1027

 

 

 

 

 

 

 

 

 

2/0

67.4

18

21.9

20

14

1.14

29.7

1176

3/0

85.0

18

23.1

16

12

1.14

31.8

1399

4/0

107

18

24.4

20

12

1.14

33.1

1615

 

 

 

 

 

 

 

 

 

250

127

35

25.8

16

10

1.14

35.5

2069

300

152

35

27.1

18

10

1.14

36.8

2307

350

177

35

28.3

20

10

1.14

38.5

2575

* The number of wires is increased where necessary to comply with the CSA 7.0 mm maximum 
   CN wire-to-wire spacing limit.


CN 15 kV 133% Al Full Neutral Electrical Properties

Conductor
Size

Stranding
(No of
Wires)

DC
Resistance
20°C
(Ω/km)

AC***
Resistance
90°C
(Ω/km,
60 Hz)

Inductive
Reactance***
(Ω/km,
60 Hz)

Capacitance
(μF/km)

Capacitive
Reactance
(MΩ∙km,
60 Hz)

AWG/
kcmil

mm²

2

33.6

solid

0.8407

1.0779

0.2335

0.1374

19300

2

33.6

7

0.8575

1.0994

0.2326

0.1405

18900

 

 

 

 

 

 

 

 

1

42.4

solid

0.6664

0.8545

0.2309

0.1461

18200

1

42.4

18

0.6798

0.8716

0.2300

0.1492

17800

 

 

 

 

 

 

 

 

1/0

53.5

solid

0.5282

0.6773

0.2280

0.1573

16900

1/0

53.5

18

0.5388

0.6909

0.2272

0.1609

16500

 

 

 

 

 

 

 

 

2/0

67.4

18

0.4275

0.5482

0.2240

0.1730

15300

3/0

85.0

18

0.3391

0.4350

0.2190

0.1877

14100

4/0

107

18

0.2689

0.3450

0.2154

0.2021

13100

 

 

 

 

 

 

 

 

250

127

35

0.2275

0.2921

0.2103

0.2187

12100

300

152

35

0.1897

0.2436

0.2071

0.2333

11400

350

177

35

0.1626

0.2090

0.2044

0.2449

10800

*** AC resistance, including skin effect, and inductive reactance are calculated 
for one isolated cable in duct, or in air or direct burial.


 TOP
   Concentric Neutral Design Options (24 kB)
   Concentric Neutral Insulation System  (60 kB)
   Concentric Neutral Jacket Thickness & Test Voltage (20 kB)
   Concentric Neutral Installation (23 kB)
   Concentric Neutral Field Testing (85 kB)



Nexans © copyright 2001 - 2012   Legal Notice | Contact Us | Site Map