CAN / CSA C68.3 - M92 CABLE CONSTRUCTION

 

 

Conductor Shield Thickness

Conductor Size AWG/kcmil Minimum Average mm Minimum at One Point  mm
Up to 4/0 0.38 0.31
250 to 500 0.51 0.41
600 to 1000 0.64 0.51

 

Insulation Thickness

Rated Cable Voltage, kV

Minimum Average Insulation Thickness 
100% Insulation Level
mm

15 4.45
25 6.60
28 7.11
46 11.30

 

Insulation Shield Thickness

Calculated Diameter Over Insulation
mm
Minimum Average
mm
Minimum at One Point

mm
25.40 or less 0.76 0.61
25.41 to 38.10 1.00 0.80
Greater than 38.10 1.25 1.00

 

Metallic Shield Area

 

Cable Type

Total Cross-Sectional Area of Concentric Neutral Wires
% of Phase Conductor Area
Copper Phase Conductor Aluminum Phase Conductor
URD 100 % 60 %
UD 33 % 20 %

The standard metallic shield of CAN/CSA C68.3-M92 cables is soft bare copper concentric neutral wires.

 

Jacket Thickness (PVC Sleeve Jacket)

Diameter Under Jacket
mm
Jacket Thickness
mm
Up to 10.80 1.1
10.81 to 17.80 1.5
17.9 to 38.0 2.0
38.1 to 64.0 2.8
64.1 and larger 3.6