Multi-conductor Ampacity rating for 3/C or 3 single conductor COPPER cables IN UNDERGROUND DUCTS

Send link to this page Your Nexans contact on this page

Ampacity Rating and Recommended Configurations

For installation of three-conductor COPPER or three single conductor COPPER cables IN UNDERGROUND DUCTS

Types RW90, RWU90 cable rated 0 to 5 kV

ATTENTION - Only these configurations are recommended by Nexans to obtain satisfactory load sharing and ampactiy.  See C.E.C. Code Rules 4-004, 8-104, 12-012, Appendix B, Appendix D14A and D14B.

Notes

The ampacities in the tables on this page are based on the following conditions:

  • 100% load factor
  • Ambient soil temperature of 20oC
  • Concrete thermal resistivity of 85oC-cm/W
  • Conductor temperature of 90oC
  • Spacing between duct centres of 190 mm
  • Top of duct bank at 760 mm below surface
  • 125 mm duct
    Neutral conductors, if required, should be included with each group of phase conductors shown (ie: use 4/C cable or 4x1/C cables).

Size AWG or kcmil Detail 1 Detail 2 Detail 3 Detail 4 Detail 5 Detail 6
1/0 (19) 180 164 152 141 131 125
2/0 (19) 206 187 172 160 149 142
3/0 (19) 235 213 196 181 168 160
4/0 (19) 269 242 223 205 190 181
250 (37) 298 267 244 225 208 198
350 (37) 361 321 293 268 248 235
500 (37) 437 386 350 319 294 279
600 (61) 480 423 383 349 321 303
750 (61) 538 471 425 386 355 335
1000 (61) 620 540 485 439 400 380
1250 (91) 676 583 521 472 433 408
1500 (91) 724 623 555 502 459 434
1750 (127) 756 648 576 521 476 449
2000 (127) 785 671 596 538 491 463

Note
1.   Allowable current for 90oC rated single copper conductor cables, or single copper conductors in contact, or multiplexed single copper conductors, installed in nonmetallic underground raceway, subject to Subrules 4-004(13) and (14), where:
(a) for any load, the cable terminates at equipment of any type other than a service box, fusible switch, circuit breaker, or panel board; or 
(b) the load is non-continuous and either end of the cable terminates at a service box, fusible switch, circuit breaker, or panel board.
2. The ampacities provided in the Table are the lesser of (a) the value obtained in accordance with Rule 4-004(1)(d); or (b) the value obtained in accordance with Rule 8-104(7).

Size AWG or kcmil Detail 1 Detail 2 Detail 3 Detail 4 Detail 5 Detail 6
100% 80%          
               
1/0 (19) 180 172 164 152 141 131 125
2/0 (19) 206 200 187 172 160 149 142
3/0 (19) 235 232 213 196 181 168 160
4/0 (19) 269 242 223 205 190 181
250 (37) 298 267 244 225 208 198
350 (37) 361 321 293 268 248 235
500 (37) 437 386 350 319 294 279
600 (61) 480 423 383 349 321 303
750 (61) 538 471 425 386 355 335
1000 (61) 620 540 485 439 400 380
1250 (91) 676 583 521 472 433 408
1500 (91) 724 623 555 502 459 434
1750 (127) 756 648 576 521 476 449
2000 (127) 785 671 596 538 491 463

Notes:

  1. Allowable current for 9oC rated multiple copper conductor cables, or single copper conductors in contact, or multiplexed single copper conductors, installed in nonmetallic raceway, subject to Subrules 4-004(13) and (14), where:
    (a) the load is continuous, and 
    (b) either end terminates at a service box, fusible switch, circuit breaker, or panel board.
  2. The columns with the heading "80%" denote that the equipment identified in 1(b) is not marked as certified to carry its ampere rating continuously.
  3. The columns with the heading "100%" denote that the equipment identified in 1(b) is marked as certified to carry its ampere rating continuously.
  4. The ampacities provide are the lesser of:  (a) the value obtained in accordance with Rule 4-004(1)(d); or (b) the value obtained in accordance with Rule 8-104(7).