Multi-conductor Ampacity for 3/C or 3 single conductor ALUMINUM cables in UNDERGROUND DUCTS

Send link to this page Your Nexans contact on this page

Ampacity Rating and Recommended Configurations

For installation of three-conductor ALUMINUM or three single conductor ALUMINUM cables IN UNDERGROUND DUCTS

Types RW90, RWU90 cable rated 0 to 5 kV

ATTENTION - Only these configurations are recommended by Nexans to obtain satisfactory load sharing and ampactiy. See C.E.C. Code Rules 4-004, 8-104, 12-012, Appendix B, Appendix Tables D15A and D15B.

Notes
The ampacities in the tables on this page are based on the following conditions:

  • 100% load factor
  • Ambient soil temperature of 20oC
  • Concrete thermal resistivity of 85oC-cm/W
  • Conductor temperature of 90oC
  • Spacing between duct centres of 190 mm
  • Top of duct bank at 760 mm below surface
  • 125 mm duct

Neutral conductors, if required, should be included with each group of phase conductors shown (ie: use 4/C cable or 4x1/C cables).

Size AWG or kcmil Detail 1 Detail 2 Detail 3 Detail 4 Detail 5 Detail 6
1/0 (18) 142 129 119 111 103 99
2/0 (18) 163 148 136 126 117 112
3/0 (18) 186 168 155 143 132 126
4/0 (18) 214 192 177 163 151 143
250 (35) 236 212 194 178 165 157
350 (35) 288 256 233 214 198 187
500 (35) 351 310 281 257 237 224
600 (58) 388 341 309 281 259 245
750 (58) 435 381 344 313 287 271
1000 (58) 502 437 392 355 326 307
1250 (91) 556 480 429 389 356 336
1500 (91) 589 514 458 415 379 358
1750 (127) 632 541 481 435 397 375
2000 (127) 660 564 501 452 413 389

Note
1. Allowable current for 90oC rated multiple aluminum conductor cables, or single aluminum conductors in contact, or multiplexed single aluminum conductors, installed in nonmetallic underground raceway, subject to Subrules 4-004(13) and (14), where:
(a) for any load, the cable terminates at equipment of any type other than a service box, fusible switch, circuit breaker, or panel board; or 
(b) the load is non-continuous and either end of the cable terminates at a service box, fusible switch, circuit breaker, or panel board.
2.  The ampacities provided in the Table are the lesser of:  (a) the value obtained in accordance with Rule 4-004(2)(d); or (b) the value obtained in accordance with Rule 8-104(7).

Size AWG or kcmil Detail 1 Detail 2 Detail 3 Detail 4 Detail 5 Detail 6
100% 80%          
               
1/0 (18) 142 133 129 119 111 103 99
2/0 (18) 163 154 148 136 126 117 112
3/0 (18) 186 179 168 155 143 132 126
4/0 (18) 214 210 192 177 163 151 143
250 (35) 236 231 212 194 178 165 157
350 (35) 288 256 233 214 198 187
500 (35) 351 310 281 257 237 224
600 (58) 388 341 309 281 259 245
750 (58) 435 381 344 313 287 271
1000 (58) 502 437 392 355 326 307
1250 (91) 556 480 429 389 356 336
1500 (91) 589 514 458 415 379 358
1750 (127) 632 541 481 435 397 375
2000 (127) 660 564 501 452 413 389

Notes:

  1. Allowable current for 90oC rated multiple aluminum conductor cables, or single aluminum conductors in contact, or multiplexed single copper conductors, installed in nonmetallic raceway, subject to Subrules 4-004(13) and (14), where:
    (a) the load is continuous, and 
    (b) either end terminates at a service box, fusible switch, circuit breaker, or panel board.
  2. The columns with the heading "80%" denote that the equipment identified in 1(b) is not marked as certified to carry its ampere rating continuously.
  3. The columns with the heading "100%" denote that the equipment identified in 1(b) is marked as certified to carry its ampere rating continuously.
  4. The ampacities provided in the Table are the lesser of:  (a) the value obtained in accordance with Rule 4-004(2) (d); or (b) the value obtained in accordance with Rule 8-104(7).