Ampacity Rating and Recommended Configurations
For installation of single conductor COPPER cables IN DIRECT BURIAL
Types RWU90, RA90, TECK90, ACWU90, 0 to 5 kV
ATTENTION - Only these configurations are recommended by Nexans to obtain satisfactory load sharing and ampactiy. See C.E.C. Code Rules 4-004, 8-104, 12-012, Appendix B, Appendix Tables D8A and D8B.
1Cable/Phase
ABC
>| |<190 mm
OOO |
2Cables/Phase
ABC CBA
OOOOOO |
2Cables/Phase
ABC CBA
>| |<610 mm
OOO OOO |
4Cables/Phase
ABC CBA
OOOOOO
OOOOOO |
4Cables/Phase
ABC CBA
>| |<610 mm OOO OOO
OOO OOO |
6Cables/Phase
ABC CBA
OOOOOO
OOOOOO
OOOOOO |
6Cables/Phase
ABC CBA
>| |<610 mm
OOO OOO
OOO OOO
OOO OOO |
| Detail 1 |
Detail 2 |
Detail 3 |
Detail 4 |
Detail 5 |
Detail 6 |
Detail 7 |
Notes:
The ampacities in the tables on this page are based on the following conditions:
- 100% load factor
- Ambient soil temperature of 20oC
- Soil resistivity of 90oC-cm/W
- Conductor temperature of 90oC
- Spacing between conductor centres of 190 mm and 610mm between groups
- Burial depth of 915 mm to centre of top cable layer
- Open circuit sheath/shield operation
Neutral conductors to be located outside of the above groups in the most convenient manner.
| Size AWG or kcmil |
Detail 1 |
Detail 2 |
Detail 3 |
Detail 4 |
Detail 5 |
Detail 6 |
Detail 7 |
| 1/0 (19) |
245 |
245 |
245 |
203 |
220 |
165 |
179 |
| 2/0 (19) |
285 |
285 |
285 |
229 |
248 |
186 |
202 |
| 3/0 (19) |
330 |
330 |
330 |
258 |
280 |
210 |
228 |
| 4/0 (19) |
385 |
385 |
385 |
291 |
315 |
236 |
256 |
| 250 (37) |
425 |
421 |
425 |
317 |
343 |
256 |
278 |
| 350 (37) |
530 |
500 |
520 |
375 |
408 |
304 |
331 |
| 500 (37) |
660 |
605 |
630 |
452 |
489 |
365 |
396 |
| 600 (61) |
740 |
659 |
682 |
491 |
534 |
397 |
433 |
| 750 (61) |
845 |
745 |
775 |
554 |
596 |
447 |
482 |
| 1000 (61) |
980 |
846 |
890 |
627 |
683 |
505 |
551 |
| 1250 (91) |
1083 |
935 |
985 |
691 |
753 |
556 |
607 |
| 1500 (91) |
1176 |
1011 |
1068 |
746 |
813 |
600 |
655 |
| 1750 (127) |
1257 |
1078 |
1140 |
793 |
865 |
637 |
696 |
| 2000 (127) |
1325 |
1133 |
1200 |
832 |
909 |
669 |
730 |
Note:
Allowable current for 90oC rated single copper conductors with spacings directly buried in earth, subject to Subrules 4-004(13) and (14), where
(a) for any load, the cable terminates at equipment of any type other than a service box, fusible switch, circuit breaker, or panelboard; or
(b) the load is non-continuous and either end of the cable terminates at a service box, fusible switch, circuit breaker, or panelboard.
2. The ampacities provided in the Tables are the lesser of: (a) the value obtained in accordance with Rule 4-004(1)(d): or (b) the value obtained in accordance with Rule 8-104(7).
Size AWG or
kcmil |
Detail 1 |
Detail 2 |
Detail 3 |
Detail 4 |
Detail 5 |
Detail 6 |
Detail 7 |
| 100% |
80% |
100% |
80% |
100% |
80% |
100% |
80% |
100% |
80% |
|
100% |
80% |
| 1/0 (19) |
208 |
172 |
208 |
172 |
208 |
172 |
203 |
172 |
208 |
172 |
165 |
179 |
172 |
| 2/0 (19) |
242 |
200 |
242 |
200 |
242 |
200 |
229 |
200 |
242 |
200 |
186 |
202 |
200 |
| 3/0 (19) |
280 |
231 |
280 |
231 |
280 |
231 |
258 |
231 |
280 |
231 |
210 |
228 |
| 4/0 (19) |
327 |
270 |
327 |
270 |
327 |
270 |
291 |
270 |
315 |
270 |
236 |
256 |
| 250 (37) |
361 |
298 |
361 |
298 |
361 |
298 |
317 |
298 |
343 |
298 |
256 |
278 |
| 350 (37) |
450 |
371 |
450 |
371 |
450 |
371 |
375 |
371 |
408 |
371 |
304 |
331 |
| 500 (37) |
561 |
462 |
561 |
462 |
561 |
462 |
452 |
489 |
462 |
365 |
396 |
| 600 (61) |
629 |
518 |
629 |
518 |
629 |
518 |
491 |
534 |
518 |
397 |
433 |
| 750 (61) |
718 |
592 |
718 |
592 |
718 |
592 |
554 |
596 |
592 |
447 |
482 |
| 1000 (61) |
850 |
700 |
846 |
700 |
846 |
700 |
627 |
683 |
505 |
551 |
| 1250 (91) |
960 |
791 |
935 |
791 |
935 |
791 |
691 |
753 |
556 |
607 |
| 1500 (91) |
1071 |
882 |
1011 |
882 |
1011 |
882 |
746 |
813 |
600 |
655 |
| 1750 (127) |
1165 |
959 |
1078 |
959 |
1078 |
959 |
793 |
865 |
637 |
696 |
| 2000 (127) |
1250 |
1029 |
1133 |
1029 |
1133 |
1029 |
832 |
909 |
669 |
730 |
Notes:
- Allowable current for 90oC rated single copper conductors with spacings directly buried in earth, subject to Subrules 4-004(13) and (14), where (a) the load is continuous, and (b) either end terminates at a service box, fusible switch, circuit breaker, or panelboard.
- The columns with the heading "80%" denote that the equipment identified in 1(b) is not marked as certified to carry its ampere rating continuously.
- The columns with the heading "100%" denote that the equipment identified in 1(b) is marked as certified to carry its ampere rating continuously.
- The ampacities provided in the Table are the lesser of: (1) the value obtained in accordance with the Rule 4-004(1)(d); or (b) the value obtained in accordance with Rule 8-104(7).
|