Single Conductor Ampacity for COPPER cables in DIRECT BURIAL

Send link to this page Your Nexans contact on this page

Ampacity Rating and Recommended Configurations

For installation of single conductor COPPER cables IN DIRECT BURIAL

Types RWU90, RA90, TECK90, ACWU90, 0 to 5 kV

ATTENTION - Only these configurations are recommended by Nexans to obtain satisfactory load sharing and ampactiy. See C.E.C. Code Rules 4-004, 8-104, 12-012, Appendix B, Appendix Tables D8A and D8B.

1Cable/Phase

ABC     
      >| |<190 mm
OOO       
2Cables/Phase

ABC CBA

OOOOOO
2Cables/Phase

ABC CBA        
    >|  |<610 mm
OOO OOO           
4Cables/Phase

ABC CBA

OOOOOO
OOOOOO
4Cables/Phase

ABC CBA        
   >|  |<610 mm
OOO OOO           
OOO OOO           
6Cables/Phase

ABC CBA

OOOOOO
OOOOOO
OOOOOO
6Cables/Phase

ABC CBA        
    >|  |<610 mm

OOO OOO          
OOO OOO          
OOO OOO           
Detail 1 Detail 2 Detail 3 Detail 4 Detail 5 Detail 6 Detail 7

Notes:

The ampacities in the tables on this page are based on the following conditions:

  • 100% load factor
  • Ambient soil temperature of 20oC
  • Soil resistivity of 90oC-cm/W
  • Conductor temperature of 90oC
  • Spacing between conductor centres of 190 mm and 610mm between groups
  • Burial depth of 915 mm to centre of top cable layer
  • Open circuit sheath/shield operation

Neutral conductors to be located outside of the above groups in the most convenient manner.

Size AWG or kcmil Detail 1 Detail 2 Detail 3 Detail 4 Detail 5 Detail 6 Detail 7
1/0 (19) 245 245 245 203 220 165 179
2/0 (19) 285 285 285 229 248 186 202
3/0 (19) 330 330 330 258 280 210 228
4/0 (19) 385 385 385 291 315 236 256
250 (37) 425 421 425 317 343 256 278
350 (37) 530 500 520 375 408 304 331
500 (37) 660 605 630 452 489 365 396
600 (61) 740 659 682 491 534 397 433
750 (61) 845 745 775 554 596 447 482
1000 (61) 980 846 890 627 683 505 551
1250 (91) 1083 935 985 691 753 556 607
1500 (91) 1176 1011 1068 746 813 600 655
1750 (127) 1257 1078 1140 793 865 637 696
2000 (127) 1325 1133 1200 832 909 669 730

Note: 
Allowable current for 90oC rated single copper conductors with spacings directly buried in earth, subject to Subrules 4-004(13) and (14), where 
(a) for any load, the cable terminates at equipment of any type other than a service box, fusible switch, circuit breaker, or panelboard; or 
(b) the load is non-continuous and either end of the cable terminates at a service box, fusible switch, circuit breaker, or panelboard.
2.  The ampacities provided in the Tables are the lesser of:  (a) the value obtained in accordance with Rule 4-004(1)(d): or (b) the value obtained in accordance with Rule 8-104(7).

Size AWG or
kcmil
Detail 1 Detail 2 Detail 3 Detail 4 Detail 5 Detail 6 Detail 7
100% 80% 100% 80% 100% 80% 100% 80% 100% 80%   100% 80%
1/0 (19) 208 172 208 172 208 172 203 172 208 172 165 179 172
2/0 (19) 242 200 242 200 242 200 229 200 242 200 186 202 200
3/0 (19) 280 231 280 231 280 231 258 231 280 231 210 228
4/0 (19) 327 270 327 270 327 270 291 270 315 270 236 256
250 (37) 361 298 361 298 361 298 317 298 343 298 256 278
350 (37) 450 371 450 371 450 371 375 371 408 371 304 331
500 (37) 561 462 561 462 561 462 452 489 462 365 396
600 (61) 629 518 629 518 629 518 491 534 518 397 433
750 (61) 718 592 718 592 718 592 554 596 592 447 482
1000 (61) 850 700 846 700 846 700 627 683 505 551
1250 (91) 960 791 935 791 935 791 691 753 556 607
1500 (91) 1071 882 1011 882 1011 882 746 813 600 655
1750 (127) 1165 959 1078 959 1078 959 793 865 637 696
2000 (127) 1250 1029 1133 1029 1133 1029 832 909 669 730

Notes:

  1. Allowable current for 90oC rated single copper conductors with spacings directly buried in earth, subject to Subrules 4-004(13) and (14), where (a) the load is continuous, and (b) either end terminates at a service box, fusible switch, circuit breaker, or panelboard.
  2. The columns with the heading "80%" denote that the equipment identified in 1(b) is not marked as certified to carry its ampere rating continuously.
  3. The columns with the heading "100%" denote that the equipment identified in 1(b) is marked as certified to carry its ampere rating continuously.
  4. The ampacities provided in the Table are the lesser of:  (1) the value obtained in accordance with the Rule 4-004(1)(d); or (b) the value obtained in accordance with Rule 8-104(7).