Ampacity Rating and Recommended Configurations
For installation of single conductor ALUMINUM cables IN DIRECT BURIAL
Types RWU90, RA90, TECK90, ACWU90, 0 to 5 kV`
ATTENTION - Only these configurations are recommended by Nexans to obtain satisfactory load sharing and ampactiy. See C.E.C. Code Rules 4-004, 8-104, 12-012, Appendix B, Appendix D9A and D9B.
1Cable/Phase
ABC
>| |<190 mm
OOO |
2Cables/Phase
ABC CBA
OOOOOO |
2Cables/Phase
ABC CBA
>| |<610 mm
OOO OOO |
4Cables/Phase
ABC CBA
OOOOOO
OOOOOO |
4Cables/Phase
ABC CBA
>| |<610 mm OOO OOO
OOO OOO |
6Cables/Phase
ABC CBA
OOOOOO
OOOOOO
OOOOOO |
6Cables/Phase
ABC CBA
>| |<610 mm
OOO OOO
OOO OOO
OOO OOO |
| Detail 1 |
Detail 2 |
Detail 3 |
Detail 4 |
Detail 5 |
Detail 6 |
Detail 7 |
Notes:
The ampacities in the tables on this page are based on the following conditions:
- 100% load factor
- Ambient soil temperature of 20oC
- Soil resistivity of 90oC-cm/W
- Conductor temperature of 90oC
- Spacing between conductor centres of 190 mm and 610 mm between groups
- Burial depth of 915 mm to centre of top cable layer
- Open circuit sheath/shield operation
Neutral conductors to be located outside of the above groups in the most convenient manner.
| Size AWG or kcmil |
Detail 1 |
Detail 2 |
Detail 3 |
Detail 4 |
Detail 5 |
Detail 6 |
Detail 7 |
| 1/0 (18) |
190 |
190 |
190 |
158 |
171 |
129 |
140 |
| 2/0 (18) |
220 |
220 |
220 |
178 |
193 |
145 |
157 |
| 3/0 (18) |
255 |
255 |
255 |
201 |
218 |
163 |
178 |
| 4/0 (18) |
300 |
300 |
300 |
227 |
246 |
183 |
200 |
| 250 (35) |
330 |
328 |
330 |
247 |
267 |
200 |
217 |
| 350 (35) |
415 |
390 |
410 |
292 |
318 |
237 |
258 |
| 500 (35) |
515 |
471 |
495 |
352 |
383 |
284 |
309 |
| 600 (58) |
585 |
513 |
541 |
382 |
419 |
308 |
340 |
| 750 (58) |
665 |
580 |
610 |
431 |
469 |
348 |
379 |
| 1000 (58) |
780 |
659 |
710 |
488 |
542 |
393 |
437 |
| 1250 (91) |
868 |
750 |
790 |
554 |
604 |
446 |
487 |
| 1500 (91) |
952 |
821 |
865 |
605 |
660 |
487 |
531 |
| 1750 (127) |
1027 |
880 |
932 |
647 |
706 |
520 |
568 |
| 2000 (127) |
1094 |
934 |
991 |
686 |
749 |
552 |
602 |
Note:
1. Allowable current for 90 oC rated single aluminum conductors with spacings directly buried in earth, subject to Subrules 4-004(13) and (14), where
(a) for any load, the cable terminates at equipment of any type other than a service box, fusible switch, circuit breaker, or panel board; or
(b) the load is non-continuous and either end of the cable terminates at a service box, fusible switch, circuit breaker, or panel board.
2. The ampacities provided in the Table are the lesser of: (a) the value obtained in accordance with Rule 4004(2)(d); or (b) the value obtained in accordance with Rule 8-104(7).
| Size AWG or kcmil |
Detail 1 |
Detail 2 |
Detail 3 |
Detail 4 |
Detail 5 |
Detail 6 |
Detail 7 |
| 100% |
80% |
100% |
80% |
100% |
80% |
100% |
80% |
100% |
80% |
|
100% |
80% |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1/0 (18) |
162 |
133 |
162 |
133 |
162 |
133 |
158 |
133 |
162 |
133 |
129 |
140 |
133 |
| 2/0 (18) |
187 |
154 |
187 |
154 |
187 |
154 |
178 |
154 |
187 |
154 |
145 |
157 |
154 |
| 3/0 (18) |
217 |
179 |
217 |
179 |
217 |
179 |
201 |
179 |
217 |
179 |
163 |
178 |
| 4/0 (18) |
255 |
210 |
255 |
210 |
255 |
210 |
227 |
210 |
246 |
210 |
183 |
200 |
| 250 (35) |
281 |
231 |
281 |
231 |
281 |
231 |
247 |
231 |
267 |
231 |
200 |
217 |
| 350 (35) |
353 |
291 |
353 |
291 |
353 |
291 |
292 |
291 |
318 |
291 |
237 |
258 |
| 500 (35) |
438 |
361 |
438 |
361 |
438 |
361 |
352 |
383 |
361 |
284 |
309 |
| 600 (58) |
498 |
410 |
498 |
410 |
498 |
410 |
382 |
419 |
410 |
308 |
340 |
| 750 (58) |
570 |
469 |
570 |
469 |
570 |
469 |
431 |
469 |
348 |
379 |
| 1000 (58) |
680 |
560 |
659 |
560 |
680 |
560 |
488 |
542 |
393 |
437 |
| 1250 (91) |
770 |
634 |
750 |
634 |
770 |
634 |
554 |
604 |
446 |
487 |
| 1500 (91) |
867 |
714 |
821 |
714 |
865 |
714 |
605 |
660 |
487 |
531 |
| 1750 (127) |
956 |
788 |
880 |
788 |
932 |
788 |
647 |
706 |
520 |
568 |
| 2000 (127) |
1037 |
854 |
934 |
854 |
991 |
854 |
686 |
749 |
552 |
602 |
Notes:
- Allowable current for 90 oC rated single aluminum conductors with spacings directly buried in earth, subject to Subrules 4-004(13) and (14), where:
(a) the load is continuous, and
(b) either end terminates at a service box, fusible switch, circuit breaker, or panel board.
- The columns with the heading "80%" denote that the equipment identified in 1(b) is not marked as certified to carry its ampere rating continuously.
- The columns with the heading "100%" denote that the equipment identified in 1(b) is marked as certified to carry its ampere rating continuously.
- The ampacities provided in the Table are the lesser of: (a) the value obtained in accordance with Rule 4-004(2)(d); or (b) the value obtained in accordance with Rule 8-104(7).
|