Single Conductor Ampacity for ALUMINUM cables in DIRECT BURIAL

Send link to this page Your Nexans contact on this page

Ampacity Rating and Recommended Configurations

For installation of single conductor ALUMINUM cables IN DIRECT BURIAL

Types RWU90, RA90, TECK90, ACWU90, 0 to 5 kV`

ATTENTION - Only these configurations are recommended by Nexans to obtain satisfactory load sharing and ampactiy. See C.E.C. Code Rules 4-004, 8-104, 12-012, Appendix B, Appendix D9A and D9B.

1Cable/Phase

ABC     
     >| |<190 mm
OOO
2Cables/Phase

ABC CBA

OOOOOO
2Cables/Phase

ABC CBA        
    
>|  |<610 mm
OOO OOO
4Cables/Phase

ABC CBA

OOOOOO
OOOOOO
4Cables/Phase

ABC CBA        
    >|  |<610 mm
OOO OOO
OOO OOO
6Cables/Phase

ABC CBA

OOOOOO
OOOOOO
OOOOOO
6Cables/Phase

ABC CBA        
    >|  |<610 mm

OOO OOO
OOO OOO
OOO OOO
Detail 1 Detail 2 Detail 3 Detail 4 Detail 5 Detail 6 Detail 7

Notes:

The ampacities in the tables on this page are based on the following conditions:

  • 100% load factor
  • Ambient soil temperature of 20oC
  • Soil resistivity of 90oC-cm/W
  • Conductor temperature of 90oC
  • Spacing between conductor centres of 190 mm and 610 mm between groups
  • Burial depth of 915 mm to centre of top cable layer
  • Open circuit sheath/shield operation

Neutral conductors to be located outside of the above groups in the most convenient manner.

Size AWG or kcmil Detail 1 Detail 2 Detail 3 Detail 4 Detail 5 Detail 6 Detail 7
1/0 (18) 190 190 190 158 171 129 140
2/0 (18) 220 220 220 178 193 145 157
3/0 (18) 255 255 255 201 218 163 178
4/0 (18) 300 300 300 227 246 183 200
250 (35) 330 328 330 247 267 200 217
350 (35) 415 390 410 292 318 237 258
500 (35) 515 471 495 352 383 284 309
600 (58) 585 513 541 382 419 308 340
750 (58) 665 580 610 431 469 348 379
1000 (58) 780 659 710 488 542 393 437
1250 (91) 868 750 790 554 604 446 487
1500 (91) 952 821 865 605 660 487 531
1750 (127) 1027 880 932 647 706 520 568
2000 (127) 1094 934 991 686 749 552 602

Note: 
1.  Allowable current for 90 oC rated single aluminum conductors with spacings directly buried in earth, subject to Subrules 4-004(13) and (14), where 
(a) for any load, the cable terminates at equipment of any type other than a service box, fusible switch, circuit breaker, or panel board; or 
(b) the load is non-continuous and either end of the cable terminates at a service box, fusible switch, circuit breaker, or panel board.
2.  The ampacities provided in the Table are the lesser of:  (a) the value obtained in accordance with Rule 4004(2)(d); or (b) the value obtained in accordance with Rule 8-104(7).

Size AWG or kcmil Detail 1 Detail 2 Detail 3 Detail 4 Detail 5 Detail 6 Detail 7
100% 80% 100% 80% 100% 80% 100% 80% 100% 80%   100% 80%
                           
1/0 (18) 162 133 162 133 162 133 158 133 162 133 129 140 133
2/0 (18) 187 154 187 154 187 154 178 154 187 154 145 157 154
3/0 (18) 217 179 217 179 217 179 201 179 217 179 163 178
4/0 (18) 255 210 255 210 255 210 227 210 246 210 183 200
250 (35) 281 231 281 231 281 231 247 231 267 231 200 217
350 (35) 353 291 353 291 353 291 292 291 318 291 237 258
500 (35) 438 361 438 361 438 361 352 383 361 284 309
600 (58) 498 410 498 410 498 410 382 419 410 308 340
750 (58) 570 469 570 469 570 469 431 469 348 379
1000 (58) 680 560 659 560 680 560 488 542 393 437
1250 (91) 770 634 750 634 770 634 554 604 446 487
1500 (91) 867 714 821 714 865 714 605 660 487 531
1750 (127) 956 788 880 788 932 788 647 706 520 568
2000 (127) 1037 854 934 854 991 854 686 749 552 602

Notes:

  1. Allowable current for 90 oC rated single aluminum conductors with spacings directly buried in earth, subject to Subrules 4-004(13) and (14), where:
    (a) the load is continuous, and 
    (b) either end terminates at a service box, fusible switch, circuit breaker, or panel board.
  2. The columns with the heading "80%" denote that the equipment identified in 1(b) is not marked as certified to carry its ampere rating continuously.
  3. The columns with the heading "100%" denote that the equipment identified in 1(b) is marked as certified to carry its ampere rating continuously.
  4. The ampacities provided in the Table are the lesser of:  (a) the value obtained in accordance with Rule 4-004(2)(d); or (b) the value obtained in accordance with Rule 8-104(7).