|
1. CORFLEX* cables should be installed using only the approved Nexans wet and dry type connectors.
For details of connectors click here.
2. Ampacity for single conductor CORFLEX*
- for cables to qualify for Table 1 and 3 (2002 C.E. Code) free air ampacity ratings, cables are required to be spaced one cable diameter (two diameters centre to centre) apart.
For details of single condutor cables in free air click here.
These are the ampacities shown in the following tables.
- for single cables in direct burial, see rule 4-004 and the notes for rule 4-004 in Appendix B & D (2002 C.E. Code).
For details of direct buried cables click here.
3. Ampacity for multi-conductor CORFLEX
- for cables to quality for Table 2 and 4 (2002 C.E. Code) free air ampacity ratings, cables are required to be spaced one cable diameter (two diameters centre to centre) apart.
These are the ampacities show in the following tables.
- for cables in direct burial, see rule 4-004 in Appendix B & D (2002 C.E. Code).
For details of direct buried cables click here.
4. The CORFLEX* sheath and connector may be used as an EQUIPMENT Bonding Conductor (not as a SYSTEM ground) and is sized to meet the requirements of the C.E. Code Table 16 (Ref. Rules 10-812 and 10-814).
When used as SERVICE ENTRANCE feeders, CORFLEX* cables should be fitted with non-ferrous grounding type bushings at the service equipment end (Ref. C.E. Code Rules 10-602 to 10-610).
For other than service entrance circuits, bonding continuity of the sheath is established through the CORFLEX* connectors.
5. Installation of any single conductor metal sheathed or armoured cables should be made with due consideration of the effects of sheath currents and of induced eddy currents in ferrous end plates. (Refer to Rules 4-008, 10-302(2) and 12-3024 and the notes on these rules in Appendix ‘B’ of the C.E. Code.)
Where sheath currents are allowed to flow in single conductor CORFLEX* cables (carrying above 425 amps). Where sheaths are isolated, it may be necessary to install a supplementary equipment bonding wire. For single conductor cables carrying more than 200 amps, non-ferrous entrance plates, connectors, bushings, washers and clamps, etc., must be used.
For Nexans' recommended derating due to sheath currents click here .
6. Minimum recommended bend radius — see CORFLEX* II Data Tables ( click here).
7. Recommended spacing of supports:
Horizontal
Single conductor cables up to 32mm (1.25") diameter:
0.91 - 1.22 m (3–4 ft.)
Single conductor cables over 32mm (1.25") diameter:
1.22 - 1.52 m (4–5 ft.)
Multi-conductor Power Cable:
1.22 - 1.52 m (4–5 ft.)
5 or more conductors Cable
0.91 - 1.22 m (3–4 ft.)
Vertical
All constructions: 1.82 - 2.44 m (6–8 ft.)
Spacing of supports for single conductor cables should be reduced from above if short circuit conditions are unusually severe.
8. Minimum recommended installation temperature minus 40°C (with suitable handling procedures). Maximum conductor temperature 90°C.
|