INSTAGLIDE® RW90 Copper

Description
(–40°C) EXELENE® XLPE Insulated Wire 90°C Service Entrance and Branch Circuit Wire
Description
Standards
National : CSA C22.2 N° 38Description
CSA File #LL23462 Class 5832 03
Single solid or compressed stranded copper with low temperature moisture resisting EXELENE® cross-linked polyethylene (XLPE) insulation. RoHS compliant.
Application
For open wiring and raceways (except cabletroughs and ventilated flexible cableway) in dry or wet locations.
For exposed wiring where exposed to weather with sunlight resistant insulation. Black and colours 6 AWG and larger are sunlight resistant and marked "SR".
Minimum recommended installation temperature minus 40°C (with suitable handling procedures).
Maximum conductor temperature 90°C.
Approved for use with ceiling fixtures. Nexans INSTAGLIDE® reduced friction construction in copper sizes 6 AWG and larger, black and colours.
Characteristics
Electrical characteristics | |
---|---|
Maximum operating voltage | 600V |
Usage characteristics | |
Minimum installation temperature | -40°C |
Maximum operating temperature | 90°C |
Specific characteristics | |
See all products | |
|
Products and services
Docs and info
INSTAGLIDE® RW90 1 kV Copper
Size |
Insulation |
Nominal |
Approximate Net |
Ampacity (Note 6) (A) 30°C Ambient |
||||||||
Free Air (Note 2) |
Conduit (Note 3) |
|||||||||||
mm |
in |
mm |
in |
kg/km |
lbs/kft |
60ºC |
75ºC |
90ºC |
60ºC |
75ºC |
90ºC |
|
14 (1) (Note 5) |
1.14 |
0.045 |
3.9 |
0.16 |
28 |
19 |
25 |
30 |
35 |
20 |
20 |
25 |
12 (1) (Note 5) |
1.14 |
0.045 |
4.4 |
0.17 |
40 |
27 |
30 |
35 |
40 |
25 |
25 |
30 |
10 (1) (Note 5) |
1.14 |
0.045 |
5.0 |
0.20 |
59 |
40 |
40 |
50 |
55 |
30 |
35 |
40 |
14 (7) (Note 5) |
1.14 |
0.045 |
4.1 |
0.16 |
28 |
19 |
25 |
30 |
35 |
20 |
20 |
25 |
12 (7) (Note 5) |
1.14 |
0.045 |
4.6 |
0.18 |
42 |
28 |
30 |
35 |
40 |
25 |
25 |
30 |
10 (7) (Note 5) |
1.14 |
0.045 |
5.2 |
0.21 |
61 |
41 |
40 |
50 |
55 |
30 |
35 |
40 |
8 (7) |
1.14 |
0.045 |
6.0 |
0.24 |
92 |
62 |
60 |
70 |
80 |
40 |
50 |
55 |
6 (7) |
1.52 |
0.060 |
7.8 |
0.31 |
149 |
100 |
80 |
95 |
105 |
55 |
65 |
75 |
4 (7) |
1.52 |
0.060 |
9.0 |
0.35 |
226 |
152 |
105 |
125 |
140 |
70 |
85 |
95 |
3 (7) |
1.52 |
0.060 |
9.7 |
0.38 |
280 |
188 |
120 |
145 |
165 |
85 |
100 |
115 |
2 (7) |
1.52 |
0.060 |
10.5 |
0.41 |
347 |
233 |
140 |
170 |
190 |
95 |
115 |
130 |
1 (19) |
2.03 |
0.080 |
12.2 |
0.48 |
439 |
295 |
165 |
195 |
220 |
110 |
130 |
145 |
1/0 (19) |
2.03 |
0.080 |
13.0 |
0.51 |
524 |
352 |
195 |
230 |
260 |
125 |
150 |
170 |
2/0 (19) |
2.03 |
0.080 |
14.1 |
0.56 |
651 |
437 |
220 |
265 |
300 |
145 |
175 |
195 |
3/0 (19) |
2.03 |
0.080 |
15.3 |
0.60 |
810 |
544 |
260 |
310 |
350 |
165 |
200 |
225 |
4/0 (19) |
2.03 |
0.080 |
16.7 |
0.66 |
1007 |
676 |
300 |
360 |
405 |
195 |
230 |
260 |
250 (37) |
2.28 |
0.090 |
18.4 |
0.72 |
1252 |
841 |
340 |
405 |
455 |
215 |
255 |
290 |
300 (37) |
2.28 |
0.090 |
20.4 |
0.80 |
1490 |
1001 |
370 |
445 |
500 |
240 |
285 |
320 |
350 (37) |
2.28 |
0.090 |
20.9 |
0.82 |
1642 |
1103 |
425 |
505 |
570 |
260 |
310 |
350 |
400 (37) |
2.28 |
0.090 |
22.8 |
0.90 |
1966 |
1321 |
455 |
545 |
615 |
280 |
335 |
380 |
500 (37) |
2.28 |
0.090 |
24.9 |
0.98 |
2433 |
1635 |
520 |
620 |
700 |
320 |
380 |
430 |
600 (61) |
2.28 |
0.090 |
26.9 |
1.06 |
2903 |
1951 |
580 |
690 |
780 |
350 |
420 |
475 |
750 (61) |
2.28 |
0.09 |
29.5 |
1.16 |
3603 |
2421 |
655 |
785 |
885 |
400 |
475 |
535 |
1000 (61) |
2.28 |
0.09 |
33.3 |
1.31 |
4764 |
3201 |
785 |
935 |
1055 |
455 |
545 |
615 |
|
INSTAGLIDE® RW90 600 V Copper
Size |
Insulation |
Nominal |
Approximate Net |
Ampacity (Note 6) (A) 30°C Ambient |
||||||||
Free Air (Note 2) |
Conduit (Note 3) |
|||||||||||
mm |
in |
mm |
in |
kg/km |
lbs/kft |
60ºC |
75ºC |
90ºC |
60ºC |
75ºC |
90ºC |
|
14 (1) (Note 5) |
0.76 |
0.030 |
3.2 |
0.13 |
24 |
16 |
25 |
30 |
35 |
20 |
20 |
25 |
12 (1) (Note 5) |
0.76 |
0.030 |
3.6 |
0.14 |
35 |
24 |
30 |
35 |
40 |
25 |
25 |
30 |
10 (1) (Note 5) |
0.76 |
0.030 |
4.1 |
0.16 |
54 |
36 |
40 |
50 |
55 |
30 |
35 |
40 |
14 (7) (Note 5) |
0.76 |
0.030 |
3.3 |
0.13 |
25 |
17 |
25 |
30 |
35 |
20 |
20 |
25 |
12 (7) (Note 5) |
0.76 |
0.030 |
3.8 |
0.15 |
37 |
25 |
30 |
35 |
40 |
25 |
25 |
30 |
10 (7) (Note 5) |
0.76 |
0.030 |
4.6 |
0.18 |
57 |
38 |
40 |
50 |
55 |
30 |
35 |
40 |
8 (7) |
1.14 |
0.045 |
5.9 |
0.23 |
92 |
62 |
60 |
70 |
80 |
40 |
50 |
55 |
6 (7) |
1.14 |
0.045 |
6.8 |
0.27 |
141 |
95 |
80 |
95 |
105 |
55 |
65 |
75 |
4 (7) |
1.14 |
0.045 |
8.0 |
0.32 |
217 |
146 |
105 |
125 |
140 |
70 |
85 |
95 |
3 (7) |
1.14 |
0.045 |
8.7 |
0.34 |
269 |
181 |
120 |
145 |
165 |
85 |
100 |
115 |
2 (7) |
1.14 |
0.045 |
9.5 |
0.37 |
336 |
226 |
140 |
170 |
190 |
95 |
115 |
130 |
1 (19) |
1.40 |
0.055 |
11.0 |
0.43 |
429 |
288 |
165 |
195 |
220 |
110 |
130 |
145 |
1/0 (19) |
1.40 |
0.055 |
11.8 |
0.47 |
532 |
358 |
195 |
230 |
260 |
125 |
150 |
170 |
2/0 (19) |
1.40 |
0.055 |
12.9 |
0.51 |
672 |
452 |
220 |
265 |
300 |
145 |
175 |
195 |
3/0 (19) |
1.40 |
0.055 |
14.2 |
0.56 |
833 |
560 |
260 |
310 |
350 |
165 |
200 |
225 |
4/0 (19) |
1.40 |
0.055 |
15.6 |
0.61 |
1040 |
699 |
300 |
360 |
405 |
195 |
230 |
260 |
250 (37) |
1.65 |
0.065 |
17.2 |
0.68 |
1238 |
832 |
340 |
405 |
455 |
215 |
255 |
290 |
300 (37) |
1.65 |
0.065 |
18.8 |
0.74 |
1454 |
977 |
370 |
445 |
500 |
240 |
285 |
320 |
350 (37) |
1.65 |
0.065 |
19.9 |
0.78 |
1713 |
1151 |
425 |
505 |
570 |
260 |
310 |
350 |
400 (37) |
1.65 |
0.065 |
21.2 |
0.84 |
1924 |
1293 |
455 |
545 |
615 |
280 |
335 |
380 |
500 (37) |
1.65 |
0.065 |
23.3 |
0.92 |
2387 |
1604 |
520 |
620 |
700 |
320 |
380 |
430 |
600 (61) |
2.03 |
0.080 |
26.0 |
1.03 |
2883 |
1937 |
580 |
690 |
780 |
350 |
420 |
475 |
750 (61) |
2.03 |
0.080 |
28.9 |
1.13 |
3582 |
2407 |
655 |
785 |
885 |
400 |
475 |
535 |
1000 (61) |
2.03 |
0.080 |
32.4 |
1.28 |
4438 |
3184 |
785 |
935 |
1055 |
455 |
545 |
615 |
|