FIREX®-II TECK90 (XLPE) -40ºC 600 Volts Composite Power and Control

Description
Nexans FIREX®-II TECK90 Cables are intended for use in various primary and secondary industries, including chemical processing plants, refineries and general factory environments.
Description
Standards
National : CSA C22.2 N° 131Description
Even in the most demanding industrial and resource industry applications, Nexans FIREX®-II TECK90 cables have proven to have a superior service and maintenance record.
FIREX®-II TECK90 Cables utilize low acid gas, low flame spread PVC jacket compounds to ensure maximum safety to personnel and equipment in the event of fire.
Applications
FIREX®-II TECK90 Cables, originally developed for use in Canadian mines, are flexible, resistant to mechanical abuse, corrosion resistant, compact and reliable. They are suitable for a wide range of applications, including ALL hazardous locations - Class I, Division 1 and 2; Class II, Division 1 and 2; and Class III.
Industries such as pulp and paper, chemical, petroleum and other primary and secondary manufacturing industries have used FIREX®-II TECK90 Cables, particularly in areas where cables are subject to the risk of mechanical damage and chemical attack.
Commercial applications for FIREX®-II TECK90 Cables include apartment buildings and commercial complexes.
FIREX®-II TECK90 Cables can be relocated easily because they are rugged and flexible. They can be used in both dry and wet locations in open wiring, in ventilated, non-ventilated and ladder-type cable troughs, in ventilated flexible cableways, and for direct burial.
TECK90 Cables are also suitable for service entrance installations - above and below ground.
Highlights
Nexans FIREX®-II TECK90 Cables are:
- Available from stock
- Versatile
- Flexible
- Resistant to Mechanical Abuse and Corrosion
- Compact and Reliable
- "HL" and "FT4" Rated per CSA
- 90°C to -40°C
- Low Acid Gas (AG14)
- Inner and outer jackets are sunlight resistant
- LEAD FREE
- RoHS compliant
Marking and Identification
The inner jackets of Nexans FIREX®-II TECK90 cables are printed: SUN RES.
The outer jackets of Nexans FIREX®-II TECK90 cables are printed: (mon/year) NEXANS FIREX®-II TECK90 XLPE (-40°C) CSA LL19376 F HL FT4 AG14 SUN RES along with conductor size, number of conductors and sequential metre marking.
Conductor Identification:
Power Conductors: Red, Black, Blue
Control Conductors: Black with Number Coding
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Electrical characteristics | |
Maximum operating voltage | 600V |
Usage characteristics | |
Maximum operating temperature | 90°C |
Docs and info
Composite TECK90 3C Power and 3C 14 or 12 AWG 600 V Control Conductors
Conductor Size |
Power Conductor |
Inner Jacket |
Nominal Diameters |
Approximate |
|||||||||
Power |
Control |
Bonding |
Inner Jacket |
Armour |
Outer Covering |
||||||||
inches |
mm |
inches |
mm |
inches |
mm |
inches |
mm |
inches |
mm |
kg/km |
|||
12 |
14 |
14 |
0.030 |
0.76 |
0.060 |
1.52 |
0.591 |
15.00 |
0.831 |
21.10 |
0.929 |
23.59 |
169 |
10 |
14 |
12 |
0.030 |
0.76 |
0.060 |
1.52 |
0.596 |
15.14 |
0.836 |
21.23 |
0.936 |
23.77 |
234 |
10 |
12 |
12 |
0.030 |
0.76 |
0.060 |
1.52 |
0.665 |
16.90 |
0.905 |
23.00 |
1.003 |
25.49 |
268 |
|
|||||||||||||
8 |
14 |
10 |
0.045 |
1.14 |
0.060 |
1.52 |
0.715 |
18.16 |
0.955 |
24.26 |
1.053 |
26.75 |
339 |
8 |
12 |
10 |
0.045 |
1.14 |
0.060 |
1.52 |
0.755 |
19.17 |
1.010 |
25.27 |
1.159 |
29.43 |
373 |
6 |
14 |
8 |
0.060 |
1.52 |
0.080 |
2.03 |
0.900 |
22.86 |
1.175 |
29.85 |
1.288 |
32.72 |
504 |
6 |
12 |
8 |
0.060 |
1.52 |
0.080 |
2.03 |
0.914 |
23.21 |
1.189 |
29.82 |
1.318 |
33.47 |
538 |
|
|||||||||||||
4 |
14 |
8 |
0.060 |
1.52 |
0.080 |
2.03 |
0.904 |
22.96 |
1.179 |
29.57 |
1.308 |
33.22 |
723 |
4 |
12 |
8 |
0.060 |
1.52 |
0.080 |
2.03 |
0.904 |
22.96 |
1.179 |
29.57 |
1.308 |
33.22 |
757 |
3 |
14 |
6 |
0.060 |
1.52 |
0.080 |
2.03 |
0.964 |
24.48 |
1.239 |
31.09 |
1.368 |
34.74 |
924 |
3 |
12 |
6 |
0.060 |
1.52 |
0.080 |
2.03 |
0.964 |
24.48 |
1.239 |
31.09 |
1.368 |
34.74 |
958 |
|
|||||||||||||
2 |
14 |
6 |
0.060 |
1.52 |
0.080 |
2.03 |
1.026 |
26.05 |
1.301 |
32.66 |
1.430 |
36.31 |
1115 |
2 |
12 |
6 |
0.060 |
1.52 |
0.080 |
2.03 |
1.026 |
26.05 |
1.301 |
32.66 |
1.430 |
36.31 |
1149 |
1 |
14 |
6 |
0.080 |
2.03 |
0.080 |
2.03 |
1.182 |
30.03 |
1.457 |
36.64 |
1.586 |
40.29 |
1361 |
1 |
12 |
6 |
0.080 |
2.03 |
0.080 |
2.03 |
1.182 |
30.03 |
1.457 |
36.64 |
1.586 |
40.29 |
1396 |
|
|||||||||||||
1/0 |
14 |
6 |
0.080 |
2.03 |
0.080 |
2.03 |
1.263 |
32.08 |
1.538 |
38.69 |
1.667 |
42.34 |
1667 |
1/0 |
12 |
6 |
0.080 |
2.03 |
0.080 |
2.03 |
1.263 |
32.08 |
1.538 |
38.69 |
1.667 |
42.34 |
1701 |
2/0 |
14 |
6 |
0.080 |
2.03 |
0.080 |
2.03 |
1.348 |
34.23 |
1.623 |
40.84 |
1.772 |
44.49 |
2055 |
2/0 |
12 |
6 |
0.080 |
2.03 |
0.080 |
2.03 |
1.348 |
34.23 |
1.623 |
40.84 |
1.772 |
44.49 |
2089 |
|
|||||||||||||
3/0 |
14 |
4 |
0.080 |
2.03 |
0.080 |
2.03 |
1.450 |
36.82 |
1.725 |
43.13 |
1.854 |
47.08 |
2615 |
3/0 |
12 |
4 |
0.080 |
2.03 |
0.080 |
2.03 |
1.450 |
36.82 |
1.725 |
43.13 |
1.854 |
47.08 |
2650 |
4/0 |
14 |
4 |
0.080 |
2.03 |
0.080 |
2.03 |
1.567 |
39.80 |
1.872 |
47.17 |
2.051 |
52.09 |
3231 |
4/0 |
12 |
4 |
0.080 |
2.03 |
0.080 |
2.03 |
1.567 |
39.80 |
1.872 |
47.17 |
2.051 |
52.09 |
3265 |
Composite TECK90 600 V Fittings and Cable Weight
Conductor Size |
Ampacity (A) |
Approx. |
Fittings |
||||||||
Power |
Control |
Bonding |
Appleton |
T&B |
CMP |
Cooper |
|||||
AWG |
AWG |
AWG |
60ºC |
75ºC |
90ºC |
lb/kft |
kg/km |
||||
12 (Note 3) |
14 |
14 |
20 |
20 |
20 |
380 |
566 |
TMC 5099 |
10466/ST050-466 |
TMC075A |
TECK050-4 |
10 (Note 3) |
14 |
12 |
30 |
30 |
30 |
414 |
616 |
TMC 5099 |
10466/ST050-466 |
TMC075A |
TECK050-4 |
10 (Note 3) |
12 |
12 |
30 |
30 |
30 |
442 |
658 |
TMC 75121 |
10467/ST075-467 |
TMC100A |
TECK075-5 |
|
|||||||||||
8 |
14 |
10 |
40 |
50 |
55 |
530 |
789 |
TMC 75121 |
10467/ST075-467 |
TMC100A |
TECK075-5 |
8 |
12 |
10 |
40 |
50 |
55 |
558 |
883 |
TMC 75121 |
10468/ST075-468 |
TMC100A |
TECK075-6 |
6 |
14 |
8 |
55 |
65 |
75 |
700 |
1042 |
TMC 100138 |
10469/ST100-469 |
TMC125A |
TECK100-7 |
6 |
12 |
8 |
55 |
65 |
75 |
843 |
1254 |
TMC 100138 |
10469/ST100-469 |
TMC125A |
TECK100-7 |
|
|||||||||||
4 |
14 |
8 |
70 |
85 |
95 |
985 |
1466 |
TMC 100138 |
10469/ST100-469 |
TMC125A |
TECK100-7 |
4 |
12 |
8 |
70 |
85 |
95 |
1001 |
1490 |
TMC 100138 |
10469/ST100-469 |
TMC125A |
TECK100-7 |
3 |
14 |
6 |
85 |
100 |
115 |
1155 |
1719 |
TMC 100138 |
10469/ST100-469 |
TMC125A |
TECK100-7 |
3 |
12 |
6 |
85 |
100 |
115 |
1172 |
1744 |
TMC 100138 |
10469/ST100-469 |
TMC125A |
TECK100-7 |
|
|||||||||||
2 |
14 |
6 |
95 |
115 |
130 |
1322 |
1967 |
TMC 125163 |
10470/ST125-470 |
TMC125A |
TECK125-8 |
2 |
12 |
6 |
95 |
115 |
130 |
1339 |
1992 |
TMC 125163 |
10470/ST125-470 |
TMC125A |
TECK125-8 |
1 |
14 |
6 |
110 |
130 |
145 |
1609 |
2394 |
TMC 125163 |
10550/ST125-550 |
TMC150A |
TECK125-8 |
1 |
12 |
6 |
110 |
130 |
145 |
1626 |
2420 |
TMC 125163 |
10550/ST125-550 |
TMC150A |
TECK125-8 |
|
|||||||||||
1/0 |
14 |
6 |
125 |
150 |
170 |
1823 |
2781 |
TMC 125188 |
10471/ST125-471 |
TMC150A |
TECK125-10 |
1/0 |
12 |
6 |
125 |
150 |
170 |
1885 |
2805 |
TMC 125188 |
10471/ST125-471 |
TMC150A |
TECK125-10 |
2/0 |
14 |
6 |
145 |
175 |
195 |
2218 |
3300 |
TMC 125188 |
10471/ST125-471 |
TMC200SA |
TECK125-10 |
2/0 |
12 |
6 |
145 |
175 |
195 |
2235 |
3326 |
TMC 125188 |
10471/ST125-471 |
TMC200SA |
TECK125-10 |
|
|||||||||||
3/0 |
14 |
4 |
165 |
200 |
225 |
2667 |
3969 |
TMC 150200 |
10472/ST150-472 |
TMC200SA |
TECK125-10 |
3/0 |
12 |
4 |
165 |
200 |
225 |
2683 |
3993 |
TMC 150200 |
10472/ST150-472 |
TMC200SA |
TECK125-10 |
4/0 |
14 |
4 |
195 |
230 |
260 |
3294 |
4902 |
TMC 150220 |
10473/ST150-473 |
TMC200A |
TECK150-12 |
4/0 |
12 |
4 |
195 |
230 |
260 |
3312 |
4929 |
TMC 150220 |
10473/ST150-473 |
TMC200A |
TECK150-12 |
Notes: |
Related documents
Selling information
Caution Notice
In case of fire, well maintained early warning smoke detectors will give an alarm long before non-metallic coverings become combustible.
However, in spite of the widespread and long-standing use of PVC in residential and commercial buildings, all purchasers of PVC insulated/ jacketed products should be aware of the following:- Non-metallic coverings of electrical cables can burn and may transmit fire when ignited.
- Burning non-metallic coverings may emit acid gases which are toxic and may generate dense smoke.
- Emission of acid gases may corrode metal in the vicinity; e.g. sensitive instruments and reinforcing rods in cement.